2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
190
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1048, p1082
Note:
When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1047, p1082
Note:
The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
Description:
Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
p1044[0...n]
CI: Motorized potentiometer setting value / Mop set val
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
- - 0
r1045
CO: Mot. potentiometer speed setp. in front of ramp-fct. gen. / Mop n_set bef RFG
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3020
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1047[0...n]
Motorized potentiometer ramp-up time / Mop ramp-up time
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
0.000 [s]
1000.000 [s]
10.000 [s]
p1048[0...n]
Motorized potentiometer ramp-down time / Mop ramp-down time
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
3020
Min Max
Factory
setting
0.000 [s]
1000.000 [s]
10.000 [s]
r1050
CO: Motorized potentiometer setpoint after ramp-function generator /
Mot poti setpoint
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3001, 3020
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......