2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
318
List Manual, 09/2017, A5E33842890
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
No protocol
4:
CAN
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
No protocol
3:
PROFIBUS
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
No protocol
7:
PROFINET
10:
EtherNet/IP
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Sets the parity for the Modbus protocol (p2030 = 2).
Value:
0:
No parity
1:
Odd parity
2:
Even parity
Note:
Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected (p2030 = 2).
p2030
Field bus interface protocol selection / Field bus protocol
CU250S_V_CAN
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 4 4
p2030
Field bus interface protocol selection / Field bus protocol
CU250S_V_DP
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 3 3
p2030
Field bus interface protocol selection / Field bus protocol
CU250S_V_PN
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 10
7
p2031
Fieldbus interface MODBUS parity / Modbus parity
CU250S_V
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 2 2
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......