2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
574
List Manual, 09/2017, A5E33842890
Index:
[0] = Message value for KDV
[1] = Processor 1 KDV actual value
[2] = Processor 2 KDV actual value
Dependency:
Refer to: C01711
Note:
The significance of the individual message values is described in message C01711.
KDV: Data cross-check
For index 1, 2:
When Safety message C01711 with message value >= 1000 occurs, these indices are not supplied with values.
Description:
Displays the checksum over the checked Safety Integrated parameters of the motion monitoring functions (actual
checksum).
Index:
[0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters for actual values
[2] = Checksum over SI parameters for hardware
Dependency:
Refer to: p9729
Refer to: F01680
Description:
Sets the checksum using the checksum-tested Safety Integrated parameters for motion monitoring functions
(reference checksum).
Index:
[0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters for actual values
[2] = Checksum over SI parameters for hardware
Dependency:
Refer to: r9728
Refer to: F01680
Description:
Displays the velocity resolution for safety-relevant motion monitoring functions.
For index 0:
Displays the safe velocity resolution (load side). Setpoints for velocity limits or parameter changes for velocities
below this threshold have no effect.
For index 1:
Displays the safe velocity accuracy based on the safe encoder accuracy
Index:
[0] = Actual velocity resolution
[1] = Minimum velocity resolution
Note:
Index 0: This parameter does not provide any information about the actual accuracy of the velocity sensing. This
depends on the type of actual value sensing, the gear factors as well as the quality of the encoder being used.
Index 1: For a two-encoder system, with just non-safety capable encoders, this means the poorer value of the two
encoders. Index[1] takes into account the coarse resolution of the encoder only
r9728[0...2]
SI Motion actual checksum SI parameters (processor 1) / SI Mtn act CRC P1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p9729[0...2]
SI Motion reference checksum SI parameters (processor 1) / SI Mtn setp CRC P1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
r9732[0...1]
SI Motion velocity resolution / SI Mtn v_res
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......