SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
351
2 Parameters
2.2 List of parameters
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2140, r2197
Description:
Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency:
Refer to: p2141, p2142, r2199
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 5" (BO: r2198.0)
"|n_act| > speed threshold value 5" (BO: r2198.1)
Dependency:
Refer to: p2150, p2158
Description:
Delay time for the comparison of the speed with the speed threshold value 5 (P2157).
Dependency:
Refer to: p2150, p2157
p2155[0...n]
Speed threshold 2 / n_thresh val 2
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8010
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]
p2156[0...n]
On delay comparison value reached / t_on cmpr val rchd
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8010
Min Max
Factory
setting
0.0 [ms]
10000.0 [ms]
0.0 [ms]
p2157[0...n]
Speed threshold 5 / n_thresh val 5
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
-
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]
p2158[0...n]
Delay for n_act comparison with speed threshold value 5 / Del compar n_5
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [ms]
10000 [ms]
10 [ms]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......