SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
269
2 Parameters
2.2 List of parameters
Description:
Sets the signal source to activate/deactivate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
When traveling to fixed stop, the fault F07900 "motor blocked" is suppressed.
Description:
Displays the torque limit to limit the speed controller output.
Index:
[0] = Upper limit
[1] = Lower limit
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Displays the limit for the torque-generating current component using the stall calculation, the current limit of the
power unit as well as the parameterization in p0640.
Index:
[0] = Upper limit
[1] = Lower limit
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Sets the signal source for the scaling of the upper torque limiting to limit the speed controller output without taking
into account the current and power limits.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
p1545[0...n]
BI: Activates travel to a fixed stop / TfS activation
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2520, 8012
Min Max
Factory
setting
- - 2683.14
r1547[0...1]
CO: Torque limit for speed controller output / M_max outp n_ctrl
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6060
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r1548[0...1]
CO: Stall current limit torque-generating maximum / Isq_max stall
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2002
Dyn. index:
-
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
-
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1552[0...n]
CI: Torque limit upper scaling without offset / M_max up w/o offs
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6060
Min Max
Factory
setting
- - 1
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......