2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
584
List Manual, 09/2017, A5E33842890
Description:
Displays the number of the cross-checked data item which caused STOP F on processor 1.
Dependency:
Refer to: F01611
Note:
A complete list of numbers for cross-checked data items appears in fault F01611.
Description:
Displays the checksum for the Safety Integrated parameters checked using checksums on processor 1 (actual
checksum).
Dependency:
Refer to: p9799, r9898
Description:
Sets the checksum for the Safety Integrated parameters checked using checksums on processor 1 (reference
checksum).
Dependency:
Refer to: r9798, p9899
Description:
Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 2.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
r9795
SI diagnostics STOP F (processor 1) / SI diag STOP F P1
Access level:
2
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2802
Min Max
Factory
setting
- - -
r9798
SI actual checksum SI parameters (processor 1) / SI act chksm P1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800
Min Max
Factory
setting
- - -
p9799
SI reference checksum SI parameters (processor 1) / SI setp_chksm P1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800
Min Max
Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p9801
SI enable functions integrated in the drive (processor 2) / SI enable fct P2
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 bin
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......