2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
310
List Manual, 09/2017, A5E33842890
Dependency:
Refer to: p0325, p0329, p1980, r1985, r1987, r1992
Note:
When the pole position identification routine is executed several times, the spread of the measured values can be
determined using this value. At the same position, the spread should be less than 2 degrees electrical.
Description:
Displays the saturation characteristic of the pole position identification routine (saturation technique).
Displays the current characteristic of the pole position identification routine (elasticity technique).
Dependency:
Refer to: p0325, p0329, p1980, r1984, r1987, r1992
Note:
PolID: Pole position identification
Regarding the saturation technique:
The values for the characteristic of the last saturation-based pole position identification routine are output every 1 ms
in order to record signals (e.g. trace).
Description:
Displays the trigger characteristic of the pole position identification routine.
The values for the characteristic of the last pole position identification routine are output every 1 ms in order to record
signals (e.g. trace).
The values for trigger characteristic and saturation characteristic are always output in synchronism from a time
perspective.
Dependency:
Refer to: p0325, p0329, p1980, r1984, r1985, r1992
Note:
PolID: Pole position identification
The following information and data can be taken from the trigger characteristic.
- the value -100% marks the angle at the start of the measurement.
- the value +100 % marks the commutation angle determined from the pole position identification routine.
Description:
Display and BICO output for the diagnostics information of the pole position identification (polID)
Dependency:
Refer to: p0325, p0329, p1980, r1984, r1985, r1987
r1985
PolID saturation curve / PolID sat_char
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
r1987
PolID trigger characteristic / PolID trig_char
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [%]
- [%]
- [%]
r1992.0...15
CO/BO: PolID diagnostics / PolID diag
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Critical encoder fault occurred
Yes
No
-
02
Encoder parking active
Yes
No
-
05
Encoder fault Class 1
Yes
No
-
06
Encoder fault Class 2
Yes
No
-
07
Pole position identification for encoder
carried out
Yes
No
-
08
Fine synchronization carried out
Yes
No
-
09
Coarse synchronization carried out
Yes
No
-
10
Commutation information available
Yes
No
-
11
Speed information available
Yes
No
-
12
Position information available
Yes
No
-
15
Zero mark passed
Yes
No
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......