2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
546
List Manual, 09/2017, A5E33842890
Description:
Sets the stop response for the function "Safe motion direction" (SDI).
This setting applies to both directions of motion.
In the case of encoderless motion monitoring (p9306 = 1), only a value of 0 or 1 is permitted.
Value:
0:
STOP A
1:
STOP B
Dependency:
Refer to: p9364, p9365
Refer to: C30716
Note:
SDI: Safe Direction (safe motion direction)
Description:
Sets the velocity tolerance limit for the "SAM" function.
SAM is deactivated once the set velocity limit has been undershot.
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the speed monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
Description:
Setting to select and de-select the acceptance test mode.
Value:
0:
[00 hex] De-select the acceptance test mode
172:
[AC hex] Select the acceptance test mode
Dependency:
Refer to: p9358, r9371
Refer to: C01799
Note:
Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives, are
enabled (p9601.2/p9801.2).
Description:
Displays the status of the acceptance test mode.
Value:
0:
[00 hex] Acc_mode inactive
12:
[0C hex] Acc_mode not possible due to POWER ON fault
13:
[0D hex] Acc_mode not possible due to incorrect ID in p9370
p9366
SI Motion SDI stop response (processor 2) / SI Mtn SDI Stop P2
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2824
Min Max
Factory
setting
0 1 1
p9368
SI Motion SAM velocity limit (processor 2) / SI Mtn SAM v_limP2
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [rpm]
1000.00 [rpm]
0.00 [rpm]
p9370
SI Motion acceptance test mode (processor 2) / SI Mtn acc_mod P2
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0000 hex
00AC hex
0000 hex
r9371
SI Motion acceptance test status (processor 2) / SI Mtn acc_stat P2
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0000 hex
00AC hex
-
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......