2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
212
List Manual, 09/2017, A5E33842890
Description:
Display and BICO output for the control word of the setpoint channel.
Description:
Displays the status word for the ramp-function generator (RFG).
Note:
For bit 02:
The bit is the result of the OR logic operation - bit 00 and bit 01.
Description:
Sets the operating mode for flying restart.
The flying restart allows the drive converter to be switched on while the motor is still rotating. In so doing, the drive
converter output frequency is changed until the actual motor speed/velocity is found. The motor then accelerates up
to the setpoint at the ramp-function generator setting.
Value:
0:
Flying restart inactive
1:
Flying restart always active (start in setpoint direction)
4:
Flying restart always active (start only in setpoint direction)
r1198.0...15
CO/BO: Control word setpoint channel / STW setpoint chan
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2505
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed setpoint bit 0
Yes
No
3010
01
Fixed setpoint bit 1
Yes
No
3010
02
Fixed setpoint bit 2
Yes
No
3010
03
Fixed setpoint bit 3
Yes
No
3010
05
Inhibit negative direction
Yes
No
3040
06
Inhibit positive direction
Yes
No
3040
11
Setpoint inversion
Yes
No
3040
13
Motorized potentiometer raise
Yes
No
3020
14
Motorized potentiometer lower
Yes
No
3020
15
Bypass ramp-function generator
Yes
No
3060,
3070
r1199.0...8
CO/BO: Ramp-function generator status word / RFG ZSW
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3001, 3080
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ramp-up active
Yes
No
-
01
Ramp-down active
Yes
No
-
02
RFG active
Yes
No
-
03
Ramp-function generator set
Yes
No
-
04
Ramp-function generator held
Yes
No
-
05
Ramp-function generator tracking active
Yes
No
-
06
Maximum limit active
Yes
No
-
07
Ramp-function generator acceleration
positive
Yes
No
-
08
Ramp-function generator acceleration
negative
Yes
No
-
p1200[0...n]
Flying restart operating mode / FlyRest op_mode
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300
Min Max
Factory
setting
0 4 0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......