SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
97
2 Parameters
2.2 List of parameters
Description:
Sets the number of bits before the absolute value in the SSI protocol.
Notice:
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description:
Sets the number of bits for the absolute value in the SSI protocol.
Notice:
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
Description:
Sets the number of bits after the absolute value in the SSI protocol.
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note:
For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description:
Sets the number of filler bits for double absolute value transfer in the SSI protocol.
Dependency:
Refer to: p0429
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note:
This parameter is only of significance for p0429.2 = 1.
p0446[0...n]
Encoder SSI number of bits before the absolute value / Enc SSI bit before
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p0447[0...n]
Encoder SSI number of bits absolute value / Enc SSI bit val
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
25
p0448[0...n]
Encoder SSI number of bits after the absolute value / Enc SSI bit after
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p0449[0...n]
Encoder SSI number of bits filler bits / Enc SSI fill bits
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
1
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......