background image

July 2, 2018
©  S&C Electric Company 1988-2018, all rights reserved

Instruction Sheet  663-590

S&C Source-Transfer PMH  

Pad-Mounted Gear

Outdoor Distribution (14.4 kV and 25 kV)

Inspection Recommendations for Units 

Equipped with Micro-AT

®

 Source-Transfer 

Control or the AT-12 Source-Transfer Control

Inspection Recommendations

Table of Contents

Section Page

Section Page

Introduction

Qualified Persons   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Read this Instruction Sheet    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Retain this Instruction Sheet    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Proper Application   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Warranty   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Warranty Qualifications    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2

Safety Information

Understanding Safety-Alert Messages    .  .  .  .  .  .  .  .  .  .  .  .  . 3
Following Safety Instructions   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
Replacement Instructions and Labels   .  .  .  .  .  .  .  .  .  .  .  .  .  . 3

Safety Precautions

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4

General

Micro-AT Source-Transfer Control   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5
AT-12 Source-Transfer Control   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5

Table 1. Inspection Procedures for Pad-Mounted 
Gear Equipped with Micro-AT Source-Transfer 
Control

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6

Table 2. Inspection Procedures for Pad-Mounted 
Gear Equipped with AT-12 Source-Transfer 
Control

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8

Table 3. Inspection and Maintenance Procedures for 
the Enclosure and for Components in High-Voltage 
Compartments

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10

Содержание PMH

Страница 1: ...Retain this Instruction Sheet 2 Proper Application 2 Warranty 2 Warranty Qualifications 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructi...

Страница 2: ...is a permanent part of your S C Source Transfer PMH Pad Mounted gear Designate a location where you can easily retrieve and refer to it Proper Application CAUTION The equipment in this publication mu...

Страница 3: ...commended recautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Inst...

Страница 4: ...y to authorized persons so that the key interlock scheme will not be comprised Key interlocks are not security locks and are not substi tutes for padlocks 5 Opening Doors Do not apply any undue force...

Страница 5: ...ctory and in the field These settings are entered into the control by means of a keypad on the front panel and may be reviewed via a liquid crystal display CAUTION When following the inspection proced...

Страница 6: ...ile still in the text menu press the Next item key one more time The Enable Test Keys item will appear on the display Press the Change key Then select On mode by pressing the Enter key The test keys a...

Страница 7: ...hen press the Next item key The date time and event ID for the last control operation will appear on the display Confirm the event ID on the display is 218 enter manual software Press the key to view...

Страница 8: ...loss of source and return of source 62P 62A and 2P Timers 1 Place the MANUAL AUTOMATIC operation selector switch in the Automatic position and note the position of the AUTOMATIC HOLD RETURN selector...

Страница 9: ...ch in the Manual position and press the OVERCURRENT LOCKOUT RESET pushbutton to cancel the lockout condition Confirm the OVERCURRENT LOCKOUT lamp extinguishes Then close the preferred source operator...

Страница 10: ...barriers are left in the slide in position for extended periods of time there is the possibility of corona discharge to the barriers Prolongedexposuretocoronadischargemaydamage the barriers and resul...

Страница 11: ...face imperfections can be burnished out Clean the blades and apply a thin layer of lubricant as necessary b Clean rotating hinge contacts and apply a thin layer of lubricant as necessary c Check conta...

Отзывы: