2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
60
List Manual, 09/2017, A5E33842890
Description:
Sets the fan run-on time after the pulses for the power unit have been canceled.
Note:
- Under certain circumstances, the fan can continue to run for longer than was set (e.g. as a result of the excessively
high heat sink temperature).
- For values less than 1 s, a 1 s run on time for the fan is active.
Description:
Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency:
Refer to: F30003
Description:
Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency:
Refer to: F30002
Description:
Selects the motor type or starts to read in the motor parameters for a motor with DRIVE-CLiQ (p0300 = 10000 or
10001, if there is a second data set).
For p0300 < 10000 the following applies:
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/AOP).
p0295
Fan run-on time / Fan run-on time
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [s]
600 [s]
0 [s]
r0296
DC link voltage undervoltage threshold / Vdc U_lower_thresh
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [V]
- [V]
- [V]
r0297
DC link voltage overvoltage threshold / Vdc U_upper_thresh
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8750, 8760, 8850,
8864, 8950, 8964
Min Max
Factory
setting
- [V]
- [V]
- [V]
p0300[0...n]
Motor type selection / Mot type sel
PM240
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS, p0130
Unit group:
-
Unit selection:
-
Func. diagram:
6310
Min Max
Factory
setting
0 10001
0
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......