SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
359
2 Parameters
2.2 List of parameters
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
Description:
Sets the delay time to evaluate the load monitoring.
p2188[0...n]
Load monitoring torque threshold 2 lower / M_thresh 2 lower
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
8013
Min Max
Factory
setting
0.00 [Nm]
20000000.00 [Nm]
0.00 [Nm]
p2189[0...n]
Load monitoring torque threshold 3 upper / M_thresh 3 upper
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
8013
Min Max
Factory
setting
0.00 [Nm]
20000000.00 [Nm]
10000000.00 [Nm]
p2190[0...n]
Load monitoring torque threshold 3 lower / M_thresh 3 lower
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
8013
Min Max
Factory
setting
0.00 [Nm]
20000000.00 [Nm]
0.00 [Nm]
p2192[0...n]
Load monitoring delay time / Load monit t_del
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8013
Min Max
Factory
setting
0.00 [s]
65.00 [s]
10.00 [s]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......