2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
340
List Manual, 09/2017, A5E33842890
Description:
Sets the third signal source to acknowledge faults.
Note:
A fault acknowledgment is triggered with a 0/1 signal.
Description:
Sets the signal source for external fault 1.
Dependency:
Refer to: F07860
Note:
An external fault is triggered with a 1/0 signal.
Description:
Sets the signal source for external fault 2.
Dependency:
Refer to: F07861
Note:
An external fault is triggered with a 1/0 signal.
Description:
Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p3110, p3111, p3112
Refer to: F07862
Note:
An external fault is triggered with a 1/0 signal.
Description:
Displays the system runtime in milliseconds when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2130, r2133, r2136
p2105[0...n]
BI: 3rd acknowledge faults / 3rd acknowledge
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2546, 8060
Min Max
Factory
setting
- - 0
p2106[0...n]
BI: External fault 1 / External fault 1
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2546
Min Max
Factory
setting
- - 1
p2107[0...n]
BI: External fault 2 / External fault 2
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2546
Min Max
Factory
setting
- - 1
p2108[0...n]
BI: External fault 3 / External fault 3
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2546
Min Max
Factory
setting
- - 1
r2109[0...63]
Fault time removed in milliseconds / t_flt resolved ms
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8050, 8060
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
Содержание SINAMICS G120
Страница 1: ...SINAMICS SINAMICS G120 CU250S 2 Control Units List Manual 09 2017 Edition www siemens com drives ...
Страница 2: ......
Страница 726: ...2 Parameters 2 6 Quick commissioning p0010 1 SINAMICS G120 CU250S 2 Control Units 726 List Manual 09 2017 A5E33842890 ...
Страница 990: ...3 Function diagrams 3 26 Data sets SINAMICS G120 CU250S 2 Control Units 990 List Manual 09 2017 A5E33842890 ...
Страница 1242: ...A Appendix A 2 List of abbreviations SINAMICS G120 CU250S 2 Control Units 1242 List Manual 09 2017 A5E33842890 ...
Страница 1255: ......