background image

EasyIO FT Series – User Reference v1.0 

 

 
 

 

 
 

 

 

 
 

 

EasyIO FT Series User Reference 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание FT Series

Страница 1: ...EasyIO FT Series User Reference v1 0 1 EasyIO FT Series User Reference...

Страница 2: ...EasyIO FT Series User Reference v1 0 2 Document Change Log 16th Jan 2018 Document created...

Страница 3: ...e headquarters or support channel Trademark Notice EasyIO logo are registered trademarks of EasyIO Holdings Pte Ltd CPT Tool is by Online Tools Inc BACnet and ASHRAE are registered trademarks of Ameri...

Страница 4: ...receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the deale...

Страница 5: ...umpers Configurations 8 Wiring diagram 9 Digital Output Wiring Connection 10 Analog Output Connection 11 Universal Input Connection 12 Network and Wireless 13 Login Details 14 Establish a connection f...

Страница 6: ...ight freeRTOS V8 2 0 OS for premium performance Supports BACnet IP server over Wi Fi and TCom or premium performance with Niagara AX and N4 The Build in boot loader can be carried out remotely No more...

Страница 7: ...ividual power supply for each controller If a single power supply is used to power up multiple EasyIO FW series make sure controller power supplies are connected with the same polarity Electrical Powe...

Страница 8: ...ptions Options are referring to IO Input Output configurations FW Model UI AO DO EIA 485 Protocol Supported FT 04B 2 1 Voltage Only 1 1 Sedona BACnet IP server Jumpers Configurations Below image shows...

Страница 9: ...EasyIO FT Series User Reference v1 0 9 Wiring diagram Below diagram shows the general wiring diagram for FT series according to its model...

Страница 10: ...or general purpose isolated digital output connections relay output Pilot Duty rating is as below Pilot Duty 24 VAC 2 0A 24 VDC 2 0A Digital Output 1 2 Channels Type Relay Contacts SPST NO 48VA at 24V...

Страница 11: ...g Output Connection EasyIO FT series has Analog Output connections Each Analog Output can only drive voltage The working range for voltage is 0 10V Universal Output 1 2 Channels Type Voltage 0 10VDC M...

Страница 12: ...ternal register settings Universal Input 2 Channel Resistance 3K 50K 10 Ohm Thermistor 10K Type 3 10K Type 2 20K All 0 1 Deg C UI as Digital Input Voltage Free Contact a Resistance The working range o...

Страница 13: ...the FT controller Access Point SSID FT xxxxxx where xxxxxx is the last 6 digit of the MAC address Mac Address label located at the bottom casing of each FT series controller The MAC address label is a...

Страница 14: ...enable It has DHCP server enable The best approach to connect to a brand new FT series controller is by utilizing its DHCP server and run automatic IP address in your device This reduces the hassle of...

Страница 15: ...escription SSID Access Point SSID name By default each SSID is named according to its MAX address You can change the SSID name to your preference PWD Access Point SSID password By default it is 123456...

Страница 16: ...ller using the above chapter Establish connection for the first time In this chapter we will guide you to connect the FT Series controller to a Wi Fi network Once this chapter is completed your FT ser...

Страница 17: ...please make sure you manage to connect to the FT controller using the above chapter Establish connection for the first time In this chapter we will guide you to connect to a EasyIO FT Series controlle...

Страница 18: ...Series Sedona programming environment Proceed to create your Sedona program installing additional kits and etc LED Indicator Colour Behaviour Description 1 Constantly Blinking at 1 Hz Device Running...