background image

 
 
 
 
 
 
 
 

 

ICP DAS 

EIP-2000 FAQ

 

 

FAQ Version 1.5 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

ICP DAS Co., Ltd.

 

2022-12-01

Содержание EIP-2000 Series

Страница 1: ...ICP DAS EIP 2000 FAQ FAQ Version 1 5 ICP DAS Co Ltd 2022 12 01...

Страница 2: ...r EIP 2000 modules 13 Q9 Is there any LabVIEW sample to EIP 2000 modules 13 Q10 What is an EDS file 14 Q11 Where can I download the EDS file of EIP 2000 14 Q12 What is the Instance ID of EIP 2000 seri...

Страница 3: ...ControlLogix Logix 5563 through the 1756 ENBT ControlLogix EtherNet IP Module successfully The configuration software is RSLogix 5000 Please follow the steps below 1 Open RSLogix 5000 and create a new...

Страница 4: ...4 3 Create a new module in the Ethernet item Figure 1 3 Create a new module 4 Select the ETHERNET MODULE below Communications in the Select Module window...

Страница 5: ...Byte count Description EIP 2055 Input Assembly 34 1st Byte DI status 2nd Byte DO status read back 3rd 34th Byte DI counters Output Assembly 2 1st Byte DO status 2nd Byte to set DI counters zero EIP 20...

Страница 6: ...21th Byte AI channel selection AI0 AI7 22th Byte AI channel selection AI8 AI15 EIP 2019 Input Assembly 20 1st 16th Byte AI status AI0 AI7 17nd 18th Byte The Brocken wire status 19rd 20th Byte CJC stat...

Страница 7: ...icpdas com products Remote_IO can_bus EtherNet_IP_series htm We provide the connection steps of Hilscher CIFX 50 RE with EIP 2055 EDS file The configuration software is SYNCON net Please refer to the...

Страница 8: ...s Figure2 3 Import Device Descriptions 4 To select the EDS file you download on our website of CD Figure2 4 Select EDS file 5 To find the EIP 2055 EDS V1 1 item below EtherNet IP Slave and drag the EI...

Страница 9: ...9 6 To configure CIFX RE EIM and EIP 2055 in the same network area Figure2 6 Network Settings 7 Right click the CIFX_RE EIM and click Download Figure2 7 Download configurations...

Страница 10: ...click the CIFX_RE EIM again and click Start Communication Figure2 8 Start Communication 9 The communication is complete You can observe the I O status on the Diagnostic window Figure2 9 I O status ob...

Страница 11: ...ith the real AI value How do I solve this problem A4 Please follow these tips to solve the problem 1 Please check the jumpers The jumpers must be at the right position If the AI type of the channel th...

Страница 12: ...ity how should I do A6 Please try the following tips 1 Disable the firewall and anti virus 2 Connect the module directly without Ethernet switch 3 Disable the Wi Fi adapters and any other Ethernet int...

Страница 13: ...ere any LabVIEW sample to EIP 2000 modules A9 Refer to Download Center Utility Tools Read_Write_accessAssemblyinstance vi The LabVIEW project is built by the NI EtherNet IP driver Please upgrade or do...

Страница 14: ...called EDS Electronic Data Sheet electronic data files It can be connected with EtherNet IP devices of other brands through EDS files Q11 Where can I download the EDS file of EIP 2000 A11 On the modul...

Страница 15: ...EIP 2042 the device IP address is 172 17 23 42 demonstration 1 Open the CMD from windows and enter the ipconfig all command 2 After the input is completed it will display which IPs are currently on th...

Страница 16: ...16 4 After removing the different network domains you can use EIP 2000 Utility to configure the device...

Страница 17: ...0 or a newer version of Utility EIP 2000 Utility download http www icpdas com tw download show php num 4842 Wireshark download https www wireshark org download html Use EIP 2019 for demonstration 1 En...

Страница 18: ...address of the EIP 2000 module for setting and connection testing without closing the firewall and Antivirus software to scan the connection information of the EIP 2000 module Q17 I can t measure the...

Страница 19: ...19 3 The external resistor is wired between VIx and AGND 4 The current can be observed by the Utility...

Отзывы: