Figure1-4. Select “ETHERNET-MODULE”.
5.
Configure the new module parameters. The I/O length of new module must be the same with the
length of EIP-2000 I/O data. The data assembly please refer to Table 1-1 and the instance ID
please refer to Table 1-2.
Figure1-5. The settings of EIP-2055
Table 1-1. Data Assembly of EIP-2000
Module
Data Assembly
Byte
count
Description
EIP-2055
Input Assembly
34
1
st
Byte: DI status
2
nd
Byte: DO status read back
3
rd
~34
th
Byte: DI counters
Output
Assembly
2
1
st
Byte: DO status
2
nd
Byte: to set DI counters zero
EIP-2060
Input Assembly
26
1
st
Byte: DI status
2
nd
Byte: DO status read back
3
rd
~26
th
Byte: DI counters
Output
Assembly
2
1
st
Byte: DO status
2
nd
Byte: to set DI counters zero
EIP-2042
Input Assembly
2
1
st
Byte:
DO status read back
(DO0~DO7).
2
nd
Byte:
DO status read back
(DO8~DO15).
Output
Assembly
2
1
st
Byte:
DO status
(DO0~DO7).
2
nd
Byte:
DO status
(DO8~DO15).