INSTALLATION
How to connect the ventilation input
Connect the ventilation input provided as shown in the diagram.
How to connect response potentiometer
:
Connect the response potentiometer of each value (max 10.000 ohm,
recommended 1 Kohm type) and connect the terminals
7-8
.
For remote connections use a standard 0.5-square millimetre two-poles wire for
each sensor, taking great care over the connections, by insulating and sealing
the joins carefully.
How to connect the contacts
Connect terminals on the terminal block (contacts up to 4AMP.AC1) to the loads
as shown in the diagram).
How to connect the line
Connect line on terminals
L-N
.
HP49
Handbook
Associative flap with feedback
SL 6.0
*
Other power voltage if you required.
230 V LINE*
Closed
Open
Common
Flap
command
Flap potentiometer
max 10 Kohm
*1
R
R
R
R
R
R
C1
C2
C3
C4
C5
C6
R
=
100 ohm resistor
C1=
Ventilation 1 contact
C2
=
Ventilation 2 contact
C3
=
Ventilation 3 contact
C4
=
Ventilation 4 contact
C5
=
Ventilation 5 contact
C6
=
Ventilation 6 contact
*1
Recommended 1 Kohm type.