A response potentiometer of each value must be applied to the flap motor.
Having done this, proceed as follows to record the potentiometer values.
Press 

ENTER

 key for at least 3 seconds:

When

 Init

 message will be displayed for more than one second release 

ENTER

key: the processor closes the flap (light 

CLOSE

 flashes) and the potentiometer

resistence value is displayed.
When the flap have completely closed, press 

ENTER

 key to record the value.

at this point the processor opens the flap (light 

OPEN

 flashes) and the potentiometer

resistence value is displayed.
When the flap has completely opened, press 

ENTER

 key to record the value.

The processor then returns automatically to the Run mode.

FLAP POTENTIOMETER INITIALIZATION PROCEDURE (Init)

ON OPEN

ON CLOSED

Lamp.

Meaning

N° Relay

Contatcts

CLOSE

Close (Heat) On

1

3-4

OPEN

Open (Cool) On

2

4-5

STATE INDICATION LAMPS

"HAND" MODE

PRESET PROGRAMS

On delivery this processor is just programmed with  the  following (variable) settings.
To return to these settings at any time:
Power off the processor, press 

ENTER 

key and keep it pressed giving power on: after

2 seconds

 boot 

message will be displayed (release now 

ENTER

 key).

The

 COSt

 values are shown in 

COSt

 paragraphs.

COSt PROGRAMMING (System constants)

*1)

 This setting corresponds to the number of ventilation steps that are connected

Mess.

Value

Meaning

Note

n.POS

6

 Number of input ventilation step

*1

POS.0

0

 Flap % position at step 0 ventilation

*2

POS.1

0

 Flap % position at step 1 ventilation

*2

POS.2

0

 Flap % position at step 2 ventilation

*2

POS.3

0

 Flap % position at step 3 ventilation

*2

POS.4

0

 Flap % position at step 4 ventilation

*2

POS.5

0

 Flap % position at step 5 ventilation

*2

POS.6

0

 Flap % position at step 6 ventilation

*2

*2)

 Program only the number of unit position (that correspond to the 

n.POS 

setting).

These settings refer  to the mode of operation of the  system and must
be made on initial start-up. Press  

- / +

 together  for  at  least  one  second:

the message 

C.O.S.t.

 will be displayed.

Press then repeatly

 ENTER 

until interested, variable's message is

displayed  (see table below) : variable value and relative message will be displayed.
Press

 + 

or

 -

 to set a new value and then 

ENTER

 to confirm.

The next system constant will then appear.
You can press 

ENTER 

for at least two seconds  to escape and return to the 

Run Mode

.

During some start-up conditions may be useful to work in "hand" mode.
Power off the processor, press

 +

 key and keep it pressed giving power on:

HAnd

  message will be displayed (release now  

 key).

Push 

 + 

 until is displayed the required number to be handed (see table relays

"

N° Relay

") and push 

ENTER

 to active the relay.

Pushing again 

 + 

 to increase another relay number previous relay is disactivated.

You can press 

ENTER

 for at least  two seconds to escape and return to the 

Run Mode.

RUN MODE

In normal condition on display appears % flap position

Example with % flap position = 24%

with the 

9-10

 terminals (see

 Installation

).

These lamps show the condition of the input's signal of
the ventilation.