SC100 System Controller 

Operation Handbook 

 
 

 

Issue: IPN 997-00012-63C 

Issue Date: August 2011 

 

 

 

 

 

 

 

Eaton Corporation

 

Telecommunications Power Solutions

 

dcpower.eaton.com

 

[email protected]

 

 

 

Содержание SC100

Страница 1: ...SC100 System Controller Operation Handbook Issue IPN 997 00012 63C Issue Date August 2011 Eaton Corporation Telecommunications Power Solutions dcpower eaton com DCinfo eaton com...

Страница 2: ...the use of existing power facilities or claims against the purchaser or user by its customers resulting from the use of the information recommendations and descriptions contained herein The informatio...

Страница 3: ...the relevant local electrical safety regulations and wiring standards Operators and maintenance staff competent in operation of dc power systems safe working practices for ac and dc powered equipment...

Страница 4: ...SC100 Handbook ii Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...

Страница 5: ...ing the Keypad and Screen 8 Navigation 8 Keypad Access Security 8 Display Settings 8 Display Time out 8 Alarm Indicators 9 SC100 Operation Using a PC Laptop 9 SC100 Identity Information 11 Chapter 3 S...

Страница 6: ...irect RS232 Communications 48 PSTN Modem Communications 49 GSM Modem Communications 51 Serial Communications RS232 Security 53 Chapter 5 Maintenance Overview 55 Troubleshooting 56 Replacing the System...

Страница 7: ...Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011 1 C h a p t e r 1 Gener al D escription Overview Topic Page SC100 System Controller 2 Input Output Board 2 Conne...

Страница 8: ...with the keypad or all settings can be changed via a PC connected to the RS232 interface see details on page 9 For connector pin outs see details on page 67 See Troubleshooting on page 56 for details...

Страница 9: ...actor 2 status LED green LVD contactor 2 connector XH5 LVD contactor 1 status LED green LVD contactor 1 connector XH4 LVD power input connector XH8 Power and RXP comms input YH11 Current sense inputs...

Страница 10: ...Fuse Fail Battery Fuse Fail AC Distribution Fan Fail AC Distribution MOV Fail Not used with SC100 Connection to temperature sensors 2 Connection to current sensors 3 Optional LVD1 contactor with or w...

Страница 11: ...on All Rights Reserved IPN 997 00012 63C August 2011 5 C h a p t e r 2 SC100 Operati on Overview Topic Page Configuration File 6 Starting the SC100 6 SC100 Operation using the Keypad and Screen 8 SC10...

Страница 12: ...y affect the performance and life expectancy of the battery must be checked and set according to the battery manufacturer s recommendations Some settings in the configuration file can be edited using...

Страница 13: ...Rights Reserved IPN 997 00012 63C August 2011 7 Any active alarms are displayed in rotation Scroll to show any other rectifiers List of any active alarms Operate control processes SC100 I O board and...

Страница 14: ...ns Set UI Access to Unprotected keypad access is allowed or Protected keypad access is denied can be temporarily over ridden see below To temporarily enable keypad access at the SC100 when access is s...

Страница 15: ...e the audible alarm indicator Either Use the keypad to go to Menu Configuration Audible Alarm Or In DCTools go to Alarms Alarm Configuration When Disabled the audible indicator will still indicate an...

Страница 16: ...ure the cable is secured so that no force is applied to the RS232 connector as this may damage the connector If COM1 port is not available or for more details see Direct RS232 Communications on page 4...

Страница 17: ...If required the following site specific information can be stored in the SC100 to assist site management Parameter Description Where to find System Manufacturer The manufacturer of the dc power system...

Страница 18: ...SC100 Handbook 12 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...

Страница 19: ...oration All Rights Reserved IPN 997 00012 63C August 2011 13 C h a p t e r 3 System Operation Overview Topic Page Voltage Control 14 Rectifiers 22 Low Voltage Disconnect LVD 27 Alarms 31 Batteries 36...

Страница 20: ...uration Set the following parameter Parameter Description Where to find Float Voltage Set to the voltage required to maintain optimum battery charge at the nominal ambient temperature as specified by...

Страница 21: ...oltage Battery Current Limit BCL Battery Current Limit automatically limits the battery recharge current to Prevent excessive battery charge current in under loaded systems Minimize gas release in VRL...

Страница 22: ...the installed C10 Battery Capacity DCTools Control Processes Battery Current Limit Engine Run Limit The Battery Current Limit setting when Engine Run is active BCL maintains the battery current below...

Страница 23: ...Lockout Remaining The time remaining until a Battery Test can be started DCTools Control Processes Battery Test Voltage Offset The adjustment to the bus voltage being applied due to the Battery Test...

Страница 24: ...Digital Inputs Configure the selected Digital Input and set Function to Start Equalize Information The following information is available about Equalize Parameter Description Where to find State Indic...

Страница 25: ...15 for details To enable Fast Charge or to stop Fast Charge manually Use the SC100 keypad to go to Menu Configuration Fast Charge Edit Or in DCTools go to Control Processes Fast Charge Information The...

Страница 26: ...y the battery manufacturer Recharge Percentage The ratio of ampere hours recharged to the ampere hours discharged Fast Charge stops either when the Ah recharged equals the Ah discharged x Fast Charge...

Страница 27: ...or inactive SC100 Menu Configuration Temp Compensation Edit DCTools Control Processes Temperature Compensation Battery Temperature The temperature measured by the battery temperature sensor SC100 Batt...

Страница 28: ...0 Un registered there is a rectifier compatibility or communications problem DCTools Rectifiers AC Voltage The ac voltage measured by the rectifier Voltage Rectifier s dc output voltage This is the Fl...

Страница 29: ...Shut Down A rectifier will shut down if its output voltage exceeds this value Recommended value is 59 2V for 48V nominal systems 28 6V for 24V nominal systems DCTools Rectifiers Ramp Up Slope The ram...

Страница 30: ...r Rectifier Shutdown is disabled The SC100 will restart a shutdown rectifier if LBRS is active See Load Based Rectifier Shutdown on page 24 Load Based Rectifier Shutdown Load Based Rectifier Shutdown...

Страница 31: ...l The time interval in hours that the SC100 will cycle rectifiers when the LBRS process is active SC100 Control Processes LBRS DCTools Rectifiers Load Based Rectifier Shutdown Redundancy If N plus 0 r...

Страница 32: ...estarted LBRS Suspend If required when LBRS is active it can be temporarily suspended for system maintenance or other reasons LBRS Suspend is not available if LBRS is Disabled Testing or Inactive To t...

Страница 33: ...se the ac phase that supplies the rectifier Phase 1 Phase 2 or Phase 3 Press Select Repeat for other rectifiers For best accuracy assign all rectifiers to the appropriate Phase To assign rectifiers to...

Страница 34: ...battery voltage reaches its minimum preset voltage LVD1 low priority load disconnect disconnects first LVD2 battery disconnect only disconnects after LVD1 Connections to high priority loads for examp...

Страница 35: ...Processes LVD To manually connect or disconnect an LVD Use the SC100 keypad to go to Menu Controls LVD1 LVD2 Control Select Manual Connect or Manual Disconnect to connect or disconnect the LVD contact...

Страница 36: ...Timer LVD1 Disconnect Voltage If the bus voltage drops to this value then any shutdown rectifiers are restarted even if LVD is disabled If the bus voltage is still lower than this value after the LVD...

Страница 37: ...emp Disconnect to Enabled as required If using PowerManagerII Groups then in DCTools go to Analog Inputs Set Auxiliary Temperature Group as required See PowerManagerII online help for details LVD1 and...

Страница 38: ...100 main screen See details on page 6 The Event Log will record the alarm activation See details on page 43 If configured an SMS text message will be sent to one or more cell phones See details on pag...

Страница 39: ...larm Indication Enable or disable the audible alarm indicator DCTools Alarms Alarm Configuration Alarm Recognition Period All alarms except those listed below are activated only after the alarm condit...

Страница 40: ...old High Float alarm is activated if the bus voltage is above this value Enable Low Float Tracking The Low Float alarm threshold will be adjusted when the operating voltage is changed by a voltage con...

Страница 41: ...In Discharge alarm will activate Always or Only While AC Present In Discharge Alarm Threshold In Discharge alarm is activated if the battery current is above this percentage of the battery capacity Se...

Страница 42: ...ity then the alarm will trigger when the load is above the System Overload Threshold for the System Overload Recognition Period If the system overload type is Redundancy then the alarm will trigger wh...

Страница 43: ...duced if the dc power system is connected to a predominantly resistive constant current load The time remaining calculation will not be correct if a non essential load is disconnected during the batte...

Страница 44: ...N A when a characterization is in progress or Battery Characterization is Disbaled Offset Voltage The adjustment to the bus voltage being applied due to the Battery Characterization While a Battery Ch...

Страница 45: ...art to start a characterization A Characterizing Battery alarm and an In Discharge alarm will be displayed The Maximum Remaining Time field will show the approximate time to the end of the characteriz...

Страница 46: ...et the following parameters Battery Characterization Enable Enabled End Voltage Set to the voltage per cell when the battery is regarded as fully discharged In general use the same value as for the LV...

Страница 47: ...s Rectifier Current Load Current otherwise it is unavailable If positive the battery is being charged Battery Temperature The temperature measured by the battery temperature sensor Auxiliary Temperatu...

Страница 48: ...nfigure a digital input 1 In DCTools go to Digital Inputs Expand the Digital Inputs table 2 Select a Digital Input 3 Configure the following parameters to suit the application To change a setting doub...

Страница 49: ...vated by any digital input analog input or system alarm mapped to it The corresponding digital output will go to the selected state until another Remote Control State is selected To configure a digita...

Страница 50: ...e a file name select a file type and browse to a location to save the file 3 Select the required interval between log entries from 5s to 60 minutes 4 Click on Start to begin the log 5 Click on Stop to...

Страница 51: ...System Operation Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011 45...

Страница 52: ......

Страница 53: ...on All Rights Reserved IPN 997 00012 63C August 2011 47 C h a p t e r 4 Communications Overview Topic Page Communications Options 48 Direct RS232 Communications 48 PSTN Modem Communications 49 GSM Mod...

Страница 54: ...tions SC100 system controller PC laptop with DCTools RS232 null modem cable See details Protocol S3P DCTools Communications Setup To connect to the SC100 with DCTools 1 Install DCTools on the PC lapto...

Страница 55: ...5 To enable modem communications 1 Connect to the SC100 with DCTools see details on page 9 2 Go to Communications 3 Click on to expand Modem Configure the following settings Enable Modem Enabled Modem...

Страница 56: ...alled Consult the modem documentation for appropriate dial modifiers DCTools or PowerManagerII Communications Setup To connect to the SC100 with DCTools or PowerManagerII 1 If not already installed in...

Страница 57: ...cess to XS1 is restricted use a DB9 ribbon cable extension Farnell part number 869 6411 GSM modem Modem Optional SMS text capable GSM cell phone SMS text message P or p Power status text messages Alar...

Страница 58: ...rs table Dialing will stop if none of the numbers in the Dial Out Number Table connect Report Retry Interval Set to the required interval between retries Dial Out Number s Type the telephone number s...

Страница 59: ...llphone write a SMS text message starting with P or p any following characters are ignored 2 Send the message to the SC100 GSM modem telephone number The SC100 will reply with a dc power system status...

Страница 60: ...ion Communications 3 Type a new password into the Write Access Password field or leave the field blank for no password control 4 Click the Apply Changes button 5 DCTools only Type the old password To...

Страница 61: ...ions to avoid short circuits or disconnection of the load equipment and follow any live working instructions applicable to the site Only perform the maintenance tasks described in the Maintenance chap...

Страница 62: ...or start up to complete See Starting the SC100 on page 6 Faulty SC100 Replace faulty SC100 SC100 Red LED or Yellow LED is on An alarm is active Check the type of alarm on the LCD or with DCTools or Po...

Страница 63: ...ight thru cable is plugged into XS1 and the modem Replace faulty cable Access to RS232 connector XS1 is restricted Use a DB9 ribbon cable extension Farnell part number 869 6411 Incorrect communication...

Страница 64: ...r circuit breaker open Check for open fuse or circuit breaker LVD contactor has disconnected the load Use DCTools to check LVD is enabled and set to correct values LVD status LED on the I O board is o...

Страница 65: ...acing the System Controller or I O Board The SC100 system controller or the I O board can be replaced without switching off the dc power system and disconnecting the equipment it powers The specific p...

Страница 66: ...SC100 Handbook 60 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...

Страница 67: ...geover contact per relay Contact Rating 0 1A 60V dc maximum Connectors Screwless terminal blocks Wire Size 0 5 2 0mm2 20 14 AWG Isolation Relay connections are isolated to 500V dc from all other circu...

Страница 68: ...esolution 50 V Accuracy 0 5 at 25 C 77 F 1 over rated temperature range Connector RJ45 Bus Voltage Sense Input IOBGP Number of Bus Voltage Sense Inputs 1 Range 60V to 60V Resolution 30mV Accuracy 0 5...

Страница 69: ...aracterization Fail The Battery Characterization process has stopped because either the battery current is unstable or the Battery Fuse Fail alarm is active or more than one rectifier has failed or th...

Страница 70: ...e is below its normal range set by the Low Float Threshold Low Load The bus voltage is lower than the safe range for the load and or battery set by the Low Load Threshold LVD Characterization Error An...

Страница 71: ...The current temperature or voltage sensing system is faulty or the I O board mapping is incorrect Standby Mode The SC100 is on but inactive Another system controller controls the dc power system If t...

Страница 72: ...SC100 Handbook 66 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...

Страница 73: ...tor Pin outs Connector Type Purpose Pin Description XS1 DB9M RS232 Serial Interface 1 2 RD Receive Data 3 TD Transmit Data 4 DTR Data Terminal Ready 5 Common Ground 6 7 RTS Request to Send 8 9 YS11 RJ...

Страница 74: ...Coil 2 Coil 3 LVD 2 auxiliary switch 4 Auxiliary switch common XH6 RJ45 Current Sense Inputs 1 Current Input 1 Common 2 Current Input 1 3 12V out 4 Current Input 2 Common 5 Current Input 2 6 0V out 7...

Страница 75: ...lly open NO 6 Relay 2 Common COM XH18 XH19 Digital relay outputs 3 4 1 Relay 3 normally closed NC 2 Relay 3 normally open NO 3 Relay 3 Common COM 4 Relay 4 normally closed NC 5 Relay 4 normally open N...

Страница 76: ...scription YH11 RJ45 RXP System Communications 1 24 48V System bus voltage 2 24 48V System bus voltage 3 4 RS485 A 5 RS485 B 6 7 0V 8 0V Digital Output 6 is also used as the Monitor Fail alarm relay It...

Страница 77: ...has become inactive Alarm number Configuration Change The configuration database was changed DI Activation A digital input alarm has become active Digital input number DI Deactivation A digital input...

Страница 78: ...SC100 Handbook 72 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...

Страница 79: ...______________________________________________________________ Location of Failure Product code ___________ Serial number __________ Document number _____________ System type installed in ____________...

Страница 80: ...____________________________________________ ______________________________________________________________________________________ ____________________________________________________________________...

Страница 81: ...office from the following list telephone 64 3 343 7448 or email CustomerServiceNZ eaton com Australia 1300 877 359 Canada 1 800 461 9166 Central America 52 55 9000 5252 China 86 571 8848 0166 86 571 8...

Страница 82: ...SC100 Handbook 76 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...

Страница 83: ...ol B Battery 35 Battery Current 6 40 54 Battery Temperature 6 21 35 Battery Temperature High Alarm 32 33 61 Battery Temperature Low Alarm 32 33 61 Battery Test 14 15 16 19 21 Characterization of Batte...

Страница 84: ...Connector 2 4 Problems See Troubleshooting Event Log System Event Types 69 F Fast Charge 14 16 19 Fast Charge Active Alarm 62 Float Voltage 14 High Float Alarm 32 33 62 Low Batt Temp Alarm 32 33 62 Fu...

Страница 85: ...31 Problems See Troubleshooting PSTN Modem Communications 47 55 R Ramp Up Slope 23 Rectifiers AC Rectifier Current Limit 23 Identify a Rectifier 23 27 Load Power 40 Load Based Rectifier Shutdown 24 L...

Страница 86: ...15 Standby Mode 63 Start Up Delay 23 System Alarms 31 33 61 System Overload Alarm 32 33 34 63 System Power 6 40 System States 41 T Target Failed to Respond Error 55 Technical Assistance 73 Temperatur...