SC100 Handbook
18
Copyright © 2008-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-63C August 2011
Equalize
Equalize charges batteries at a higher voltage after they have been fully charged to ensure that
all individual cell voltages are the same, that electrolyte is distributed evenly, and that sulfate
crystal buildup on the plates is reduced.
Equalize can be scheduled to occur at regular intervals and/or can be started/stopped
manually.
Refer to the battery manufacturer's instructions before using Equalize.
If a Digital Input has the function "Start Equalize" then a manual equalize cycle will start when
the Digital Input becomes active.
► To enable Equalize (or to start or stop Equalize manually)
Use the SC100 keypad to go to:
Menu > Configuration > Equalize > Edit
.
Or, in DCTools go to:
Control Processes >
Equalize
.
► To use an external relay contact to activate an Equalize (optional)
Connect a voltage free relay contact or switch to any Digital Input.
In DCTools go to:
Digital Inputs
.
Configure the selected Digital Input and set
Function
to
Start Equalize
.
Information
The following information is available about Equalize.
Parameter
Description
Where to find:
State
Indicates if Equalize is Disabled, Active or Inactive.
SC100*: Menu > Controls >
Equalize
DCTools: Control Processes
> Equalize
Next Start
The time to the start of the next scheduled Equalize.
Remaining Time
The time to the end of the currently active Equalize.
Voltage Offset
The adjustment to the bus voltage being applied due to
the Equalize.
DCTools: Control Processes
> Equalize
*Only if Equalize is Enabled.
Configuration
Set the following parameters.
Parameter
Description
Where to find:
Interval
The time between scheduled Equalize. The interval
period begins at the start of an Equalize. Zero disables
scheduled Equalizes.
SC100: Menu >
Configuration > Equalize >
Edit
DCTools: Control Processes
> Equalize
Duration
The duration of a scheduled Equalize. Use the value
recommended by the battery manufacturer.
Equalize Voltage
The bus voltage maintained during an Equalize cycle.
Use the value recommended by the battery
manufacturer. The bus voltage is further adjusted by
Temperature Compensation.
Содержание SC100
Страница 18: ...SC100 Handbook 12 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 51: ...System Operation Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011 45...
Страница 52: ......
Страница 66: ...SC100 Handbook 60 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 72: ...SC100 Handbook 66 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 78: ...SC100 Handbook 72 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 82: ...SC100 Handbook 76 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...