System Operation
Copyright © 2008-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-63C August 2011
43
► To test a digital output
In DCTools go to
Digital Outputs
:
Expand the
Digital Outputs
table.
In the
Test State
column select
Relay Active
or
Relay Inactive
.
The corresponding digital output will go to the selected state for the
Test Duration
period (default: 10s), or until another
Test State
is selected.
Or, use the SC100 keypad to go to
Menu
>
Controls
>
Digital Output Test
>
Activate.
Select the required Digital Output (1-6).
Press
Toggle
to change the state of the digital output.
The corresponding digital output will go to the selected state for the
Test Duration
period (default: 10s), or until Toggle is pressed again.
► To set the state of a digital output
In DCTools or PowerManagerII (SiteManager) go to
Digital Outputs
:
Expand the
Digital Outputs
table.
In the
Remote Control State
column select
Active
or
Inactive
.
If Inactive is selected the digital output will still be activated by any digital input, analog
input, or system alarm mapped to it.
The corresponding digital output will go to the selected state until another
Remote
Control State
is selected.
► To configure a digital output
1
In DCTools go to
Digital Outputs
. Expand the
Digital Outputs
table.
2
Select a Digital Output*.
3
Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Test State
Set to
Test Disabled
.
Remote Control State
Set to
Inactive
.
Name
Type the name of the output.
Active State
Select the state of the output when the Digital Output is active*.
Group
Set to 0 unless using Groups in PowerManagerII. See PowerManagerII
online help for details.
* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board
loses power or loses communication with the SC100.
Data Logging
The SC100 has the following data logging functions.
Event Log
The SC100 maintains an Event Log in non-volatile memory. The Event Log records up to 100
system events (oldest events are over-written). See System Event Types on page
description of event log entries.
Содержание SC100
Страница 18: ...SC100 Handbook 12 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 51: ...System Operation Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011 45...
Страница 52: ......
Страница 66: ...SC100 Handbook 60 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 72: ...SC100 Handbook 66 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 78: ...SC100 Handbook 72 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 82: ...SC100 Handbook 76 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...