Maintenance
Copyright © 2008-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-63C August 2011
57
Problem
Possible Cause
Required Action
SC100 or DCTools displays
???
or
N/A
Failed, disconnected or
unconfigured sensor.
Replace, connect or configure sensor.
Faulty or disconnected voltage
feed module.
Replace or connect voltage feed module.
SC100 displays
Config Error
Missing or invalid configuration
file.
Either:
Load a valid configuration file into the
SC100. See Backup and Restore on page
, or
Change one or more configuration
settings using the SC100 keypad or
DCTools.
Incorrect rectifier voltage,
because installed rectifiers have
different output voltages.
Check that all rectifiers are of the same
type and replace as necessary.
DCTools connection
problem (
Target Failed to
Respond
error)
Connection problem
Refer to following communications
problems.
Modem/RS232
communications problem.
Incorrect, disconnected or faulty
cable.
Check an RS232 straight-thru cable is
plugged into XS1 and the modem.
Replace faulty cable.
Access to RS232 connector XS1
is restricted.
Use a DB9 ribbon cable extension (Farnell
part number 869-6411).
Incorrect communications
settings.
See PSTN Modem Communications on
page
Communications on page
Incorrect modem setup string.
Refer to the AT command section in the
modem's manual.
Modem not powered or other
modem problem.
Refer to the modem's manual.
Incompatible modem.
Contact your Eaton dc product supplier
or Eaton for advice. See Worldwide
Support on page
Password required to change
settings.
See Write Access Password on page
I/O board Power/Comms
OK LED is off
I/O board is not powered or
faulty.
Check connection to YH3 on I/O board.
See Connections on page
Replace I/O board if faulty.
I/O board Power/Comms
OK LED is flashing.
I/O board is responding to an
Identify
command from the
SC100.
None, this is normal operation. See
details.
LVD Status LED(s) (on I/O
board) are on.
LVD contactor is energized.
None, this is normal operation.
LVD Status LED(s) are off
(I/O board Power On LED is
on).
LVD contactor is de-energized. None, this is normal operation.
Содержание SC100
Страница 18: ...SC100 Handbook 12 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 51: ...System Operation Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011 45...
Страница 52: ......
Страница 66: ...SC100 Handbook 60 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 72: ...SC100 Handbook 66 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 78: ...SC100 Handbook 72 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...
Страница 82: ...SC100 Handbook 76 Copyright 2008 2011 Eaton Corporation All Rights Reserved IPN 997 00012 63C August 2011...