SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
135
2 Parameters
2.2 List of parameters
Description:
Displays the number of motor pole pairs. The value is used for internal calculations.
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor, etc.
Dependency:
For p0314 > 0, the entered value is displayed in r0313.
For p0314 = 0, the pole pair number (r0313) is automatically calculated from the rated power (p0307), rated
frequency (p0310) and rated speed (p0311).
Refer to: p0307, p0310, p0311, p0314
Note:
For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency is
zero.
Description:
Sets the motor pole pair number.
p0314 = 1: 2-pole motor
p0314 = 2: 4-pole motor, etc.
Dependency:
For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice:
If p0314 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010 =
3).
For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0:
The torque constant is calculated from the motor data.
p0316 > 0:
The selected value is used as torque constant.
Dependency:
Refer to: r0334
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
This parameter is not used for induction motors (p0300 = 1xx).
r0313[0...n]
Motor pole pair number, actual (or calculated) / Mot PolePairNo act
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
5300
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p0314[0...n]
Motor pole pair number / Mot pole pair No.
VECTOR_G
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 255
0
p0316[0...n]
Motor torque constant / Mot kT
VECTOR_G
Can be changed:
C2(1, 3), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
28_1
Unit selection:
p0100
Not for motor type:
ASM, SESM, REL,
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [Nm/A]
400.000 [Nm/A]
0.000 [Nm/A]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......