2 Parameters
2.2 List of parameters
SINAMICS G130/G150
414
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the scaling of the signal source for the motoring and negative regenerative power limit.
0 signifies no power limiting.
Description:
Sets the threshold for the accelerating torque for the moment of inertia estimator.
The moment of inertia estimator is active above this threshold.
The value is referred to the rated torque (r0333).
Dependency:
Refer to: p1400, p1561, p1562
Note:
The moment of inertia estimation is inaccurate at very low accelerating torques. As a consequence, below this
threshold, the estimator does not provide any new values.
Description:
Sets the change time for the moment of inertia for the moment of inertia estimator.
Lower values mean that faster changes are possible.
For a higher value, this estimated value is smoothed more significantly.
Dependency:
Refer to: p1400, p1560, p1562
Description:
Sets the change time for the load torque for the moment of inertia estimator.
Lower values mean that faster changes are possible.
For a higher value, this estimated value is smoothed more significantly.
Dependency:
Refer to: p1400, p1560, p1561
p1556[0...n]
Power limit scaling / P_max scal
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6640
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 340.28235E36
0.00
p1560[0...n]
Moment of inertia estimator accelerating torque threshold value / J_est M thresh
VECTOR_G
(J_estimator)
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.10 [%]
100.00 [%]
10.00 [%]
p1561[0...n]
Moment of inertia estimator change time moment of inertia / J_est t J
VECTOR_G
(J_estimator)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
10.00 [ms]
5000.00 [ms]
500.00 [ms]
p1562[0...n]
Moment of inertia estimator change time load / J_est t load
VECTOR_G
(J_estimator)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
5.00 [ms]
5000.00 [ms]
10.00 [ms]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......