SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1365
4 Faults and alarms
4.1 Overview of faults and alarms
Drive object:
Each message (fault/alarm) specifies the drive object in which it can be found.
A message can belong to either one, several, or all drive objects.
Component
Type of hardware component that has triggered the fault or alarm.
With "Component: None" it is not possible to assign the message to a hardware component.
Propagation
In the case of faults that are, for example, triggered by the Control Unit or a Terminal Module,
central functions of the drive are also often affected. Using propagation, faults that are
triggered by one drive object are therefore passed on to other drive objects.
There are the following types of propagation:
•
BICO
The fault is passed on to all active drive objects with closed-loop control functions (infeed,
drive) to which there is a BICO interconnection.
•
DRIVE
The fault is passed on to all active drive objects with closed-loop control functions.
•
GLOBAL
The fault is passed on to all active drive objects.
Error in the parameterization/configuration/commissioning
procedure (18)
An error was identified in the parameterization or in a commissioning
procedure, or the parameterization does not match the actual device
configuration. Determine the precise cause of the fault using the
commissioning tool. Adapt the parameterization or device
configuration.
9011
17
31
16
15
General drive fault (19)
Group fault. Determine the precise cause of the fault using the
commissioning tool.
9012
18
9
9
15
Auxiliary unit fault (20)
The monitoring of an auxiliary unit (incoming transformer, cooling
unit …) has detected an illegal state. Determine the exact cause of the
fault and check the relevant device.
9013
19
29
26
15
1. Undervoltage condition of the electronics power supply
2. Overvoltage condition of the electronics power supply
Table 4-4
Message classes and coding of various diagnostic interfaces, continued
Text of the message class (number according to PROFIdrive)
Cause and remedy.
Diagnostics interface
PN
(hex)
DS1
(dec)
DP
(dec)
ET 200
(dec)
NAMUR
(r3113.x)
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......