SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
271
2 Parameters
2.2 List of parameters
Implementation:
MDS0: p0827[0] = 4, interconnect output to switch contactor 0 to r0830.4, p0831[4] = "input, feedback signal,
contactor 0"
MDS1: p0827[1] = 5, interconnect output to switch contactor 1 to r0830.5, p0831[5] = "input, feedback signal,
contactor 1"
The following sequence applies when changing over from MDS0 to MDS1:
1. Status bit r0830.4 is deleted. When the feedback signal (p0831[4]) is connected, the system waits until the
feedback signal "contactor open" is displayed. If the feedback signal is not connected, then the system waits for the
switch-off interlocking time of 320 ms.
2. Status bit r0830.5 is set. If the feedback signal (p0831[5]) is connected, the system waits until the feedback signal
"contactor closed" is displayed. If the feedback signal is not connected, then the system waits for the switch-on
interlocking time of 160 ms.
Index:
[0] = Feedback signal contactor 0
[1] = Feedback signal contactor 1
[2] = Feedback signal contactor 2
[3] = Feedback signal contactor 3
[4] = Feedback signal contactor 4
[5] = Feedback signal contactor 5
[6] = Feedback signal contactor 6
[7] = Feedback signal contactor 7
[8] = Feedback signal contactor 8
[9] = Feedback signal contactor 9
[10] = Feedback signal contactor 10
[11] = Feedback signal contactor 11
[12] = Feedback signal contactor 12
[13] = Feedback signal contactor 13
[14] = Feedback signal contactor 14
[15] = Feedback signal contactor 15
Description:
Displays the status word of the contactor feedback signals when changing over a motor.
Dependency:
Refer to: p0831
r0832.0...15
CO/BO: Mot. changeover contactor feedback sig. status word / Mot_chng fdbk ZSW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8575
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Feedback signal contactor 0
Closed
Opened
-
01
Feedback signal contactor 1
Closed
Opened
-
02
Feedback signal contactor 2
Closed
Opened
-
03
Feedback signal contactor 3
Closed
Opened
-
04
Feedback signal contactor 4
Closed
Opened
-
05
Feedback signal contactor 5
Closed
Opened
-
06
Feedback signal contactor 6
Closed
Opened
-
07
Feedback signal contactor 7
Closed
Opened
-
08
Feedback signal contactor 8
Closed
Opened
-
09
Feedback signal contactor 9
Closed
Opened
-
10
Feedback signal contactor 10
Closed
Opened
-
11
Feedback signal contactor 11
Closed
Opened
-
12
Feedback signal contactor 12
Closed
Opened
-
13
Feedback signal contactor 13
Closed
Opened
-
14
Feedback signal contactor 14
Closed
Opened
-
15
Feedback signal contactor 15
Closed
Opened
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......