S
IN
A
MICS
G1
30/G150
List
Manual (LH
2)
, 07/2
016
, A5E0326347
9A
13
45
3
F
un
ction dia
g
ra
ms
3.
26
Te
rm
inal Mo
dule
120
(T
M1
20)
F
ig.
3
-218
96
06 – Te
mp
erature evalu
ation
cha
nne
ls
2
a
nd
3 (KT
Y
/PT
C
/bimetal
)
- 9606 -
Function diagram
8
7
6
5
4
3
2
1
fp_9606_51_eng.vsd
SINAMICS
11.02.16 V04.08.00
X521.5
X521.6
Temperature sensor channel 2
r4101[2]
r4104.5
r4104.4
T = 64 ms
2 mA
KTY/PTC/
Bimetal/PT1000
Channel 2
-
+
+ temp
- temp
Sensor type
p4100[2]
<1>
Terminal Module 120 (TM120) - Temperature evaluation channels 2 and 3
DO: TM120
A35213
"Temperature
alarm threshold
channel 2
exceeded"
A35922
"Error temperature sensor channel 2"
F35209
"Temperature
fault/alarm
threshold channel 2
exceeded"
r4105[2]
Temperature actual
value channel 2
<2>
Alarm is not present
Measured temperature
Alarm is present
-300 °C
A
D
Resistance
calculation
1
T
0
p4103[2]
<5>
Channel 2 alarm threshold
-48...251 [°C]
p4102[4] (251)
<4>
X521.7
X521.8
KTY/PTC/
Bimetal/PT1000
Channel 3
1
0
Temperature sensor channel 3
r4101[3]
T = 64 ms
2 mA
-
+
+ temp
- temp
Sensor type
p4100[3]
<1>
A
D
Resistance
calculation
<6>
<6>
<6>
0
1
r4104.7
r4104.6
A35214
"Temperature
alarm threshold
channel 3
exceeded"
A35923
"Error temperature sensor channel 3"
F35210
"Temperature
fault/alarm
threshold channel 3
exceeded"
r4105[3]
Temperature actual
value channel 3
<2>
Alarm is not present
Measured temperature
Alarm is present
-300 °C
1
T
0
p4103[3]
<5>
Channel 3 alarm threshold
-48...251 [°C]
p4102[6] (251)
<4>
1
0
<6>
0
1
Channel 3 fault threshold
-48...251 [°C]
p4102[7] (251)
0
1
5 K
Channel 2 fault threshold
-48...251 [°C]
p4102[5] (251)
0
1
5 K
<1> p4100[0...3]
= 0: Evaluation disabled
= 1: PTC
= 2: KTY
= 4: Bimetal break contact
= 6: PT1000
<2> An alarm A35922 or A35923 in the temperature evaluation channel 2 or 3 of
the TM120 is signaled to the next (downstream) drive control via the special
temperature actual value -300 °C.
<3> As a result of the wire breakage monitoring the maximum temperature that
can be measured is limited to approximate 188.6 °C.
<4> A value > 250 °C de-activates the alarm or fault.
4000.00 μs
<5> For KTY/PT1000: p4103[0...3] = 0 Output from Timer always off (0).
For PTC/bimetal: p4103[0...3] = 0 delay time = 0 s.
<6> KTY/PT1000 = For monitoring wire breakage and short-circuit.
PTC = For monitoring short-circuit.
Bimetal = No monitoring.
KTY
188.6 °C
-140 °C
KTY
PTC
Bimetal
-300 °C
PTC
Bimetal
-50 °C
250 °C
1
0
R
T
<3>
PTC: 1650 Ohm
Bimetal: 100 Ohm
0
1
<1>
188.6 °C
-99 °C
R
T
<3>
6
2
1
0
4
KTY
188.6 °C
-140 °C
KTY
PTC
Bimetal
-300 °C
PTC
Bimetal
-50 °C
250 °C
1
0
R
T
<3>
PTC: 1650 Ohm
Bimetal: 100 Ohm
0
1
<1>
188.6 °C
-99 °C
R
T
<3>
6
2
1
0
4
PT1000
PT1000
Sensortype
p4100
Sensortype
p4100
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......