SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
395
2 Parameters
2.2 List of parameters
Description:
Sets the adaptation factor before the adaptation range (0 % ... p1456) to additionally adapt the P gain of the
speed/velocity controller.
Dependency:
Refer to: p1455, p1456, p1457, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
Description:
Sets the adaptation factor after the adaptation range (> p1457) to additionally adapt the P gain of the speed/velocity
controller.
Dependency:
Refer to: p1455, p1456, p1457, p1458
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
Description:
Sets the P gain of the speed controller before the adaptation speed range (0 ... p1464).
This value corresponds to the basic setting of the P gain of the speed controller without adaptation (p1461 = 100 %).
Dependency:
For p0528 = 1, the speed controller gain is represented without any dimensions.
Refer to: p1461, p1464, p1465
Description:
Sets the P gain of the speed controller for the upper adaptation speed range (> p1465).
The entry is made referred to the P gain for the lower adaptation speed range of the speed controller (% referred to
p1460).
Dependency:
Refer to: p1460, p1464, p1465
Note:
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
p1464, then the controller gain below p1465 is adapted with p1461. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
p1458[0...n]
Adaptation factor lower / Adapt_factor lower
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200000.0 [%]
100.0 [%]
p1459[0...n]
Adaptation factor upper / Adapt_factor upper
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200000.0 [%]
100.0 [%]
p1460[0...n]
Speed controller P gain adaptation speed lower / n_ctrl Kp n lower
VECTOR_G
(J_estimator, n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6020, 6040
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 999999.000
0.300
p1461[0...n]
Speed controller Kp adaptation speed upper scaling / n_ctr Kp n up scal
VECTOR_G
(J_estimator, n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200000.0 [%]
100.0 [%]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......