4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1630
List Manual (LH2), 07/2016, A5E03263479A
For fault value = 2:
- adapt the speed setpoint (p1965) or adapt the minimum limit (p1080).
For fault value = 3:
- adapt the speed setpoint (p1965) or suppression (skip) bandwidths (p1091 ... p1094, p1101).
For fault value = 4:
- adapt the speed setpoint (p1965) or maximum limit (p1082, p1083 and p1086).
For fault value = 5:
- flux setpoint p1570 = 100 % and current setpoint p1610 = 0 % kept during the Lq measurement.
For fault value = 6:
- reduce the regenerative load so that the drive does not reach field weakening when accelerating.
- reduce p1965 so that the q leakage inductance is recorded at lower speeds.
For fault value = 7:
- increase p1082, if this is technically permissible.
- reduce p1965 so that the q leakage inductance is recorded at lower speeds.
For fault value = 8:
- reduce the load when motoring so that the drive is not braked.
- increase p1965 so that the measurement may be taken at higher speeds.
Note:
The measurement of the q leakage inductance can be disabled using p1959.5. If only p1959.5 is set, then only this
measurement is carried out if p1960 is set to 1, 2 and the drive is switched on.
See also: p1959 (Rotating measurement configuration)
F07990
Drive: Incorrect motor data identification
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Motor
Propagation:
GLOBAL
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred during the identification routine.
Fault value (r0949, interpret decimal):
1: Current limit value reached.
2: Identified stator resistance lies outside the expected range 0.02 ... 100% of Zn.
3: Identified rotor resistance lies outside the expected range 0.1 ... 100% of Zn. Separately excited synchronous
motors: damping resistance outside 1.0 ...15 % of Zn.
4: Identified stator reactance lies outside the expected range 50 ... 900 % of Zn. Separately excited synchronous
motors: stator reactance outside 20 ...500 % of Zn.
5: Identified magnetizing reactance lies outside the expected range 50 ... 900 % of Zn. Separately excited
synchronous motors: magnetizing reactance outside 20 ...500 % of Zn.
6: Identified rotor time constant lies outside the expected range 10 ms ... 5 s. Separately excited synchronous
motors: damping time constant outside of 5 ms ... 1 s.
7: Identified total leakage reactance lies outside the expected range 4 ... 100 % of Zn.
8: Identified stator leakage reactance lies outside the expected range 2 ... 50% of Zn. Separately excited
synchronous motors: stator leakage reactance outside 2 ...40 % of Zn.
9: Identified rotor leakage reactance lies outside the expected range 2 ... 50% of Zn. Separately excited synchronous
motors: damping leakage reactance outside 1.5 ...20 % of Zn.
10: Motor has been incorrectly connected.
11: Motor shaft rotates.
12: Ground fault detected.
15: Pulse inhibit occurred during motor data identification.
16: during the Rs measurement an error occurred when activating one or several power modules connected in
parallel.
17: after the Rs measurement an error occurred when activating one or several power modules connected in parallel.
20: Identified threshold voltage of the semiconductor devices lies outside the expected range 0 ... 10 V.
30: Current controller in voltage limiting.
40: At least one identification contains errors. The identified parameters are not saved to prevent inconsistencies.
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......