SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1677
4 Faults and alarms
4.2 List of faults and alarms
For fault value = 1951:
- operate the module in the permissible range.
- replace the Motor Module involved.
For fault value = 1952:
- replace the Motor Module involved.
For fault value = 2000, 2001, 2002, 2003:
- check the discrepancy time, and if required, increase the value (p9650/p9850, p9652/p9852).
- check the wiring of the safety-relevant inputs (SGE) (contact problems).
- check why STO was selected in r9872. When the SMM functions are active (p9501 = 1), STO can also be selected
using these functions.
- replace the Motor Module involved.
Note:
This fault can be acknowledged after removing the cause of the error and after correct selection/deselection of STO.
For fault value = 6000 ... 6999:
Refer to the description of the message values in safety message C01611.
Note:
CU: Control Unit
EP: Enable Pulses (pulse enable)
ESR: Extended Stop and Retract
MM: Motor Module
SGE: Safety-relevant input
SI: Safety Integrated
SMM: Safe Motion Monitoring
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
STO: Safe Torque Off / SH: Safe standstill
Reaction upon A:
NONE
Acknowl. upon A:
NONE
N30620 (F, A)
SI P2: Safe Torque Off active
Message value:
-
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Safe Torque Off" (STO) function of the basic functions has been selected in monitoring channel 2 using the
input terminal and is active.
Note:
- this message does not result in a safety stop response.
- this message is not output when STO is selected using the Extended Functions.
Remedy:
Not necessary.
Note:
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill
Reaction upon F:
OFF2
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......