SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
461
2 Parameters
2.2 List of parameters
Description:
Defines the maximum modulation depth.
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
If optimized pulse patterns are enabled (edge modulation), then the modulation depth is limited to below the output
frequency of 28 Hz as there is no optimized pulse pattern in this range.
Description:
Filter time constant for the smoothed modulation index to change over the modulator mode.
Description:
Sets the filter time constant for the DC link voltage.
This time constant is used to calculate the modulation depth.
Description:
DC link voltage that is used to convert the setpoint voltage into an equivalent modulation depth.
Description:
DC link voltage used to determine the maximum possible output voltage.
p1803[0...n]
Maximum modulation depth / Modulat depth max
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6723
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
20.0 [%]
150.0 [%]
100.0 [%]
p1804[0...n]
Filter time constant smoothed modulation index / T_filt mod_idx sm
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [ms]
10000.0 [ms]
10.0 [ms]
p1806[0...n]
Filter time constant Vdc correction / T_filt Vdc_corr
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [ms]
10000.0 [ms]
0.0 [ms]
r1807
Actual DC link voltage to calculate the modulation depth / VdcActValMod_depth
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
5_2
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [V]
- [V]
- [V]
r1808
DC link voltage actual value for U_max calculation / Vdc act val U_max
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
5_2
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [V]
- [V]
- [V]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......