2 Parameters
2.2 List of parameters
SINAMICS G130/G150
634
List Manual (LH2), 07/2016, A5E03263479A
Description:
Exits the quick commissioning (p0010 = 1) with automatic calculation of all of the parameters that depend on the
entries made during the quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning. The interconnections of
PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700 are re-established and all of the
dependent filter and closed-loop control parameters are calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the end of quick commissioning.
Value:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick param. (only) for controller par. and reset for BICO par
3:
Completion of quick commissioning
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
Description:
Differential voltage for calibrating the offset for DC link voltage measurement.
Dependency:
Refer to: r0192, p0212
Caution:
Incorrect use of the calibration can have a negative impact on the closed-loop control.
The parameter influences the upper and lower voltage detection.
Note:
Parameter entries are directly saved in the DRIVE-CLiQ component involved.
The parameter is only effective in the case of booksize power units, if r0192.22 = 1 and p0212.0 = 1.
Description:
Displays the commissioning steps that have been carried out.
p3900
Completion of quick commissioning / Compl quick_comm
B_INF
Can be changed:
C2(1)
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
p3901[0...n]
Power unit EEPROM Vdc offset calibration / PU EEPROM Vdc offs
VECTOR_G, B_INF
Can be changed:
C1, C2(1), T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
All groups
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-40.0 [V]
40.0 [V]
0.0 [V]
r3925[0...n]
Identification final display / Ident final_disp
VECTOR_G
Can be changed:
-
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Unsigned32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Yes
No
-
02
Motor data identification carried out at
standstill (p1910 = 1)
Yes
No
-
03
Rotating measurement carried out (p1960 =
1, 2)
Yes
No
-
04
Motor encoder adjustment carried out
(p1960 = 1, p1990 = 1, 3)
Yes
No
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......