219
2 Parameters
2.2 List of parameters
Description:
Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0496, r0497, r0498
Description:
Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Dependency:
Refer to: p0496, r0497, r0498
Description:
Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0578.
Value:
0:
Standard drive (VECTOR)
1:
Pumps and fans
2:
Sensorless closed-loop control down to f = 0 (passive loads)
4:
Dynamic in the field weakening range
5:
Starting with a high break loose torque
6:
High LoadMomInert
Dependency:
Refer to: p2175, p2177
Note:
The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5 (for p0500 = 6: p0340 = 1, 3, 4)
- when writing p0578 = 1
For p0500 = 0 and when the calculation is initiated, the following parameters are set:
- p1574 = 10 V (separately excited synchronous motor: 20 V)
- p1750.2 = 0
- p1802 = 4 (SVM/FLB without overcontrol)
- p1803 = 106 %
- p1610 = 50 %
- p1611 = 30 %
- p1310 = 50 %
r0499[0...2]
CO: Encoder diagnostic signal high word / Enc diag high word
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r0499
Encoder diagnostic signal high word / Enc diag high word
ENC
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p0500
Technology application / Tec application
VECTOR_G
Can be changed:
C2(1, 5), T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Applications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 6
1
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......