SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
137
2 Parameters
2.2 List of parameters
Description:
Sets the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
Note:
The parameter has no effect for induction motors.
The parameter has not effect for synchronous motors if a value of 0.0 is entered. The user-selectable current limit is
entered into p0640.
Description:
Sets the maximum speed for the winding.
The following applies when calculating the maximum speed (p1082):
- for p0324 = 0 or p0532 = 0, p0322 is used.
- for p0324 > 0 and p0532 > 0, the minimum value from the two parameters is used.
Dependency:
Refer to: p0322, p0532, p1082
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0324 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3).
Description:
Sets the current for the 1st phase of the two-stage technique for pole position identification routine.
The current of the 2nd phase is set in p0329.
The two-stage technique is selected with p1980 = 4.
Dependency:
Refer to: p0329, p1980, p1982, r1984, r1985, r1987, p1990
Notice:
When the motor code (p0301) is changed, it is possible that p0325 is not pre-assigned.
p0325 can be pre-assigned using p0340 = 3.
Note:
The value is automatically pre-assigned for the following events:
- For p0325 = 0 and automatic calculation of the closed-loop control parameters (p0340 = 1, 2, 3).
- for quick commissioning (p3900 = 1, 2, 3).
p0323[0...n]
Maximum motor current / Mot I_max
VECTOR_G
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, SESM, RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Arms]
20000.00 [Arms]
0.00 [Arms]
p0324[0...n]
Winding maximum speed / Winding n_max
VECTOR_G
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [rpm]
210000.0 [rpm]
0.0 [rpm]
p0325[0...n]
Motor pole position identification current 1st phase / Mot PolID I 1st ph
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [Arms]
10000.000 [Arms]
0.000 [Arms]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......