2 Parameters
2.2 List of parameters
SINAMICS G130/G150
316
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source for the speed limit of the positive direction on the ramp-function generator input.
Note:
The OFF3 ramp-down time (p1135) is effective when the limit is reduced.
Description:
Sets the signal source for the speed limit of the negative direction on the ramp-function generator input.
Note:
The OFF3 ramp-down time (p1135) is effective when the limit is reduced.
Description:
Sets the signal source for jog 1.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1058
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
Description:
Sets the signal source for jog 2.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1051[0...n]
CI: Speed limit RFG positive direction of rotation / n_limit RFG pos
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3050
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- -
1083[0]
p1052[0...n]
CI: Speed limit RFG negative direction of rotation / n_limit RFG neg
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3050
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- -
1086[0]
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
2501, 3030
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
2501, 3030
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......