SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
389
2 Parameters
2.2 List of parameters
Description:
Sets the dead time to symmetrize the speed setpoint for active torque pre-control.
The selected multiplier refers to the sampling time of the speed controller (dead time= p1428 * p0115[1]).
Dependency:
In conjunction with p1429, this parameter can emulate the characteristics of how the torque is established (dynamic
response of closed current control loop).
The parameter is only effective if the acceleration model is supplied using external acceleration signals (p1400.2 =
1). For p1400.2 = 0, a fixed dead time is used.
Refer to: p1429, p1511
Description:
Sets the time constant (PT1) for symmetrizing the speed setpoint for active torque pre-control.
Dependency:
In conjunction with p1428, this parameter can emulate the characteristics of how torque is established (dynamic
response of the closed current control loop).
For VECTOR (r0107) the following applies:
The parameter is only effective if the acceleration model is supplied using external acceleration signals (p1400.2 =
1). For p1400.2 = 0, time constant p1442 (or p1452 for sensorless vector control) is used.
Refer to: p1428, p1511
Description:
Displays the speed setpoint for pre-controlling the motor model with sensorless vector control.
Note:
With p1400.15 = 0 or encoderless torque control, the pre-control signal is kept continuously in the range of the
voltage model.
Description:
Sets the natural frequency of a PT2 element for the reference model of the speed controller.
Recommendation:
The reference model is correctly set when the characteristics of p1439 (reference model output) and p1445 (actual
speed value) are virtually identical when the I component of the speed controller is disabled.
p1428[0...n]
Speed pre-control balancing dead time / n_prectrBal t_dead
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6031
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 3.0
0.0
p1429[0...n]
Speed pre-control balancing time constant / n_prectr bal T
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
5030, 5042,
5210, 6031
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
10000.00 [ms]
0.00 [ms]
r1431
CO: Speed pre-control to motor model / n_prectrl mot_mod
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6030
P-Group:
Closed-loop control
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1433[0...n]
Speed controller reference model natural frequency / n_ctrl RefMod fn
VECTOR_G
(J_estimator, n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6031
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [Hz]
8000.0 [Hz]
0.0 [Hz]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......