2 Parameters
2.2 List of parameters
Description:
Sets the delay time for switching in the DC link fast discharge for an internal Braking Module.
Dependency:
Refer to: p3681
Notice:
The parameter is only effective for Basic Line Modules with the internal Braking Module (this is valid for Basic Line
Modules with a power rating of less than 100 kW).
Description:
Sets the activation threshold for the braking chopper.
Note:
The activation threshold is only effective if the "Device supply voltage reduced" function (p0212.0 = 1) has been
activated!
Description:
The binector output uses a 1 signal to indicate that 80 % of the highest permissible I2t value has been reached in the
Braking Module.
Dependency:
Refer to: A06905
Description:
The binector output uses a 1 signal to indicate an overcurrent fault or an I2t shutdown in the Braking Module.
Dependency:
Refer to: F06906
p3682
Braking Module internal DC link fast discharge delay time / BM int DC dischg t
B_INF
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
500 [ms]
4294967295 [ms]
1000 [ms]
p3683
Braking Module internal activation threshold brake chopper / BM int act thresh
B_INF
Can be changed:
C2(1)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
110.00 [V]
780.00 [V]
760.00 [V]
r3685
BO: Digital Braking Module: Pre-alarm I2t shutdown / Dig BM A I2t shutd
B_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r3686
BO: Digital Braking Module fault / Dig BM fault
B_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......