SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
139
2 Parameters
2.2 List of parameters
Description:
Displays the rated motor slip.
Dependency:
The rated slip is calculated from the rated frequency, rated speed and number of pole pairs.
Refer to: p0310, p0311, r0313
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
Description:
Induction motor:
Displays the rated magnetizing current from p0320.
For p0320 = 0, the internally calculated magnetizing current is displayed.
Synchronous motor:
Displays the rated short-circuit current from p0320.
Dependency:
If p0320 was not entered, then the parameter is calculated from the rating plate parameters.
Note:
In the case of multi-motor operation r0331 is increased by the factor p0306 compared to p0320.
Description:
Displays the rated power factor for induction motors.
For IEC motors, the following applies (p0100 = 0):
For p0308 = 0, the internally calculated power factor is displayed.
For p0308 > 0, this value is displayed.
For NEMA motors, the following applies (p0100 = 1, 2):
For p0309 = 0, the internally calculated power factor is displayed.
For p0309 > 0, this value is converted into the power factor and displayed.
Dependency:
If p0308 is not entered, the parameter is calculated from the rating plate parameters.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
r0330[0...n]
Rated motor slip / Mot slip_rated
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, SESM, REL,
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r0331[0...n]
Actual motor magnetizing current/short-circuit current / Mot I_mag_rtd act
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
5722, 6722,
6724
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
r0332[0...n]
Rated motor power factor / Mot cos phi rated
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......