4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1494
List Manual (LH2), 07/2016, A5E03263479A
A01943
PB/PN: clock cycle signal error when establishing bus communication
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram.
The global control telegram for synchronization is being irregularly received.
-.the master is sending an irregular global control telegram.
- the master is using another clock synchronous DP clock cycle than was transferred to the slave in the
parameterizing telegram.
Remedy:
- check the master application and bus configuration.
- check the consistency between the clock cycle input when configuring the slave and clock cycle setting at the
master.
Note:
PB: PROFIBUS
PN: PROFINET
A01944
PB/PN: sign-of-life synchronism not reached
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram.
Synchronization with the master sign-of-life (STW2.12 ... STW2.15) could not be completed because the sign-of-life
is changing differently to how it was configured in the Tmapc time grid.
Remedy:
- ensure that the master correctly increments the sign-of-life in the master application clock cycle Tmapc.
- correct the interconnection of the master sign-of-life (p2045).
Note:
PB: PROFIBUS
PN: PROFINET
A01945
PROFIBUS: Connection to the Publisher failed
Message value:
Fault cause: %1 bin
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
For PROFIBUS peer-to-peer data transfer, the connection to at least one Publisher has failed.
Alarm value (r2124, interpret binary):
Bit 0 = 1: Publisher with address in r2077[0], connection failed.
...
Bit 15 = 1: Publisher with address in r2077[15], connection failed.
Remedy:
- check the PROFIBUS cables.
- carry out a first commissioning of the Publisher that has the failed connection.
See also: r2077 (PROFIBUS diagnostics peer-to-peer data transfer addresses)
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......