2 Parameters
2.2 List of parameters
SINAMICS G130/G150
322
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets skip speed 2.
Dependency:
Refer to: p1091, p1093, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets skip speed 3.
Dependency:
Refer to: p1091, p1092, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets skip speed 4.
Dependency:
Refer to: p1091, p1092, p1093, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets the signal source for scaling the skip speeds.
Dependency:
Refer to: p1091, p1092, p1093, p1094
p1092[0...n]
Skip speed 2 / n_skip 2
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3050
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1093[0...n]
Skip speed 3 / n_skip 3
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3050
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1094[0...n]
Skip speed 4 / n_skip 4
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3050
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1098[0...n]
CI: Skip speed scaling / n_skip scal
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3050
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......