SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
691
2 Parameters
2.2 List of parameters
Description:
Sets the characteristic type.
For non-linear sensors, the interrelationship between the signal voltage and the position can be defined using a third
degree polynomial.
Value:
0:
Characteristic inactive
1:
Characteristic polynomial third degree
Dependency:
Refer to: p4663, p4664, p4665, p4666
Note:
If value = 1:
A third degree polynomial is defined as follows:
F(x) = K3 * x^3 + K2 * x^2 + K1 * x + K0
Coefficients K0 ... K3 should be defined and entered into p4663 ... p4666.
The sensor range is emulated to x = -0.5 ... +0.5.
Description:
Setting for coefficient K0 to calculate the characteristic (p4662).
Dependency:
Refer to: p4662, p4664, p4665, p4666
Description:
Setting for coefficient K1 to calculate the characteristic (p4662).
Dependency:
Refer to: p4662, p4663, p4665, p4666
Description:
Setting for coefficient K2 to calculate the characteristic (p4662).
Dependency:
Refer to: p4662, p4663, p4664, p4666
p4662[0...n]
Encoder characteristic type / Enc char_type
VECTOR_G, ENC
Can be changed:
C2(4)
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p4663[0...n]
Encoder characteristic K0 / Enc char K0
VECTOR_G, ENC
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p4664[0...n]
Encoder characteristic K1 / Enc char K1
VECTOR_G, ENC
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p4665[0...n]
Encoder characteristic K2 / Enc char K2
VECTOR_G, ENC
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......