SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
435
2 Parameters
2.2 List of parameters
Description:
Displays the torque generating current setpoint Iqset after the torque limits and the clock cycle interpolation is ahead
of the current setpoint filters.
Description:
Displays the torque setpoint of the function generator.
Description:
Sets the minimum smoothing time constant for the setpoint of the torque-generating current components.
Description:
Sets the smoothing time constant for the setpoint of the torque-generating current components.
Note:
The smoothing time does not become effective until the field-weakening range is reached.
Description:
Sets the signal source for tuning the natural frequency of the current setpoint filter 1, 2 and speed actual value filter 5.
Index:
[0] = Filter 1
[1] = Filter 2
[2] = Reserved
[3] = Reserved
[4] = Filter 5
r1650
Current setpoint torque-generating before filter / Iq_set before filt
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
5710
P-Group:
Closed-loop control
Unit group:
6_2
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
r1651
CO: Torque setpoint function generator / M_set FG
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
7_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
p1653[0...n]
Current setpoint torque-generating smoothing time minimum / Isq_s T_smth min
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6710
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.1 [ms]
20.0 [ms]
0.1 [ms]
p1654[0...n]
Curr. setpoint torque-gen. smoothing time field weakening range / Isq_s T_smth FW
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6710
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.1 [ms]
50.0 [ms]
4.8 [ms]
p1655[0...4]
CI: Current setpoint/Speed actual value filter nat. frequency tuning / I/n_setp_filt f_n
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
6700, 6710
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......