2 Parameters
2.2 List of parameters
SINAMICS G130/G150
964
List Manual (LH2), 07/2016, A5E03263479A
Description:
Displays the Safety Integrated version for the safe monitoring functions.
Index:
[0] = Safety Version (major release)
[1] = Safety Version (minor release)
[2] = Safety Version (baselevel or patch)
[3] = Safety Version (hotfix)
Dependency:
Refer to: r9770, r9870, r9890
Note:
Example:
r9590[0] = 2, r9590[1] = 60, r9590[2] = 1, r9590[3] = 0 --> SI Motion version V02.60.01.00
Description:
Sets the enable signals for the safety functions integrated in the drive and the type of selection on the Control Unit.
Not all of the settings listed below will be permissible, depending on the Control Unit and Motor Module or Power
Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions via Terminal Module 54F (TM54F) have been enabled (permissible for r9771.5 = 1).
0005 hex:
Extended functions via Terminal Module 54F (TM54F) and the basic functions via onboard terminals have been
enabled (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
0024 hex:
Extended functions without selection are enabled (permissible for r9771.16 = 1).
0025 hex:
Extended functions without selection and basic functions via onboard terminals are enabled (permissible for r9771.16
= 1).
0040 hex:
Basic functions are enabled via TM54F
0041 hex:
Basic functions are enabled via TM54F and basic functions via onboard terminals.
r9590[0...3]
SI Motion version safety motion monitoring (Control Unit) / SI Mtn version CU
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p9601
SI enable functions integrated in the drive (Control Unit) / SI enable fct CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0000 bin
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......