4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1766
List Manual (LH2), 07/2016, A5E03263479A
Bit 11: Parity error.
Bit 12: Data line signal level error during the monoflop time.
Bit 13: Data line incorrect.
Bit 14: Fault for the register communication.
Bit 15: Internal communication error.
Note:
For an EnDat 2.2 encoder, the significance of the fault value for F3x135 (x = 1, 2, 3) is described.
Remedy:
For fault value, bit 0 = 1:
- Enc defect F31111 may provide additional details.
For fault value, bit 1 = 1:
- incorrect encoder type / replace the encoder or encoder cable.
For fault value, bit 2 = 1:
- incorrect encoder type / replace the encoder or encoder cable.
For fault value, bit 3 = 1:
- EMC / connect the cable shield, replace the encoder or encoder cable.
For fault value, bit 4 = 1:
- EMC / connect the cable shield, replace the encoder or encoder cable, replace the Sensor Module.
For fault value, bit 5 = 1:
- EMC / connect the cable shield, replace the encoder or encoder cable, replace the Sensor Module.
For fault value, bit 6 = 1:
- Update Sensor Module firmware.
For fault value, bit 7 = 1:
- incorrect encoder type / replace the encoder or encoder cable.
For fault value, bit 8 = 1:
- check parameterization (p0429.2).
For fault value, bit 9 = 1:
- EMC / connect the cable shield, replace the encoder or encoder cable, replace the Sensor Module.
For fault value, bit 10 = 1:
- check parameterization (p0429.2, p0449).
For fault value, bit 11 = 1:
- check parameterization (p0436).
For fault value, bit 12 = 1:
- check parameterization (p0429.6).
For fault value, bit 13 = 1:
- check data line.
For fault value, bit 14 = 1:
- incorrect encoder type / replace the encoder or encoder cable.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32111 (N, A)
Encoder 2: Absolute encoder internal fault
Message value:
Fault cause: %1 bin, additional information: %2
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
VECTOR_G
Component:
Encoder 2
Propagation:
LOCAL
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
PULSE INHIBIT
Cause:
The absolute encoder fault word supplies fault bits that have been set.
For p0404.8 = 0, the following applies:
Fault value for internal Siemens troubleshooting.
For p0404.8 = 1, the following applies:
Fault value (r0949, interpret binary):
yyyyxxxx hex: yyyy = supplementary information, xxxx = fault cause
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......