SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
607
2 Parameters
2.2 List of parameters
Description:
Sets the total DC link capacitance for closed-loop voltage control.
The capacitance of one power unit is pre-assigned to this value. The value should be adapted according to the
number of power units.
Note:
The controller setting for the DC link voltage controller is derived from this value.
Description:
Sets the delay time for the ON/OFF1 command of the infeed.
After ON/OFF1 = 0 the infeed remains in operation for the specified time
Dependency:
Refer to: p0840
Notice:
The ON/OFF1 command of the infeed can be interrupted.
Note:
This parameter is only relevant if a Motor Module and the infeed are controlled by the same OFF command. In this
case, the delay time and the stop ramp time of the motor can be coordinated with one another.
Description:
Sets the setpoint for the DC link voltage on the motor side.
Description:
Sets the signal source for the supplementary setpoint for the DC link voltage on the motor side.
Dependency:
Refer to: p3510
p3422
DC link capacitance total / C_DC tot
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.20 [mF]
2000.00 [mF]
2.00 [mF]
p3490
Infeed delay time OFF1 command / INF t_del OFF1
B_INF
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8732, 8832,
8932
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [ms]
1000000.0 [ms]
0.0 [ms]
p3510
DC link voltage setpoint / Vdc setp
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7960
P-Group:
Closed-loop control
Unit group:
5_2
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
100.00 [V]
1600.00 [V]
600.00 [V]
p3511
CI: DC link voltage supplementary setpoint / Vdc Z_set
VECTOR_G
(Tech_ctrl)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
7960
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- -
0
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......