2 Parameters
2.2 List of parameters
SINAMICS G130/G150
208
List Manual (LH2), 07/2016, A5E03263479A
Notice:
Information on Gn_STW/Gn_ZSW should be taken from the corresponding product documentation.
Note:
The signal source for the encoder control word is set with p0480.
Description:
Sets the input terminal to connect probe 1.
Value:
0:
No meas probe
1:
DI/DO 9 (X122.10/X121.8)
2:
DI/DO 10 (X122.12/X121.10)
3:
DI/DO 11 (X122.13/X121.11)
4:
DI/DO 13 (X132.10/X131.2)
5:
DI/DO 14 (X132.12/X131.4)
6:
DI/DO 15 (X132.13/X131.5)
7:
DI/DO 8 (X122.9/X121.7)
8:
DI/DO 12 (X132.9/X131.1)
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0489, p0728
Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
To select the values:
For CX32, NX10 and NX15, only DI/DO 8, 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
Note:
DI/DO: Bidirectional Digital Input/Output
The terminal must be set as input (p0728).
Refer to the encoder interface for PROFIdrive.
If parameterization is rejected, check whether the terminal is already being used in p0580, p0680, p2517 or p2518.
Description:
Sets the input terminal to connect probe 1.
Value:
0:
No meas probe
1:
DI/DO 9 (X122.10/X121.8)
2:
DI/DO 10 (X122.12/X121.10)
3:
DI/DO 11 (X122.13/X121.11)
4:
DI/DO 13 (X132.10/X131.2)
5:
DI/DO 14 (X132.12/X131.4)
6:
DI/DO 15 (X132.13/X131.5)
7:
DI/DO 8 (X122.9/X121.7)
8:
DI/DO 12 (X132.9/X131.1)
Dependency:
Refer to: p0489, p0728
06
Request command bit 2
Yes
No
-
07
Flying measurement mode/search for
reference mark
Flying measurement
Reference marks
-
13
Request absolute value cyclic
Yes
No
-
14
Request parking encoder
Yes
No
-
15
Request acknowledge encoder fault
Yes
No
-
p0488[0...2]
Measuring probe 1 input terminal / Meas probe 1 inp
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
4740
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 8
0
p0488
Measuring probe 1 input terminal / Meas probe 1 inp
ENC
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
4740
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 8
0
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......