2 Parameters
2.2 List of parameters
SINAMICS G130/G150
118
List Manual (LH2), 07/2016, A5E03263479A
p0230 = 3:
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sine-wave filter capacitance) = filter capacitance
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
--> p1802 (modulator modes) = space vector modulation without overcontrol
--> p1811 (modulator configuration) = wobbulation amplitude
--> p1909 (motor data identification, control word) = only Rs measurement
p0230 = 4:
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1802 (modulator modes) = space vector modulation without overcontrol
--> p1811 (modulator configuration) = wobbulation amplitude
--> p1909 (motor data identification, control word) = only Rs measurement
The user must set the following parameters according to the data sheet of the sine-wave filter and also the user must
check whether they are permitted.
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sine-wave filter capacitance) = filter capacitance
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note:
Only motor reactor filter type can be selected for a synchronous reluctance motor (RESM).
if a filter type cannot be selected, then this filter type is not permitted for the Motor Module.
p0230 = 1:
The output frequency of booksize power units with output reactors is restricted to 120 Hz, for blocksize and chassis
power units, to 150 Hz. The maximum pulse frequency for booksize and blocksize power units is 4 kHz, for chassis
power units, twice the rated pulse frequency (2.5 kHz or 4 kHz).
p0230 = 2:
Chassis power units with dv/dt filter, depending on the rated pulse frequency, may be operated with a maximum
pulse frequency of p1800 = 2.5 kHz or 4 kHz. The output frequency is limited to 150 Hz.
p0230 = 3:
Sine-wave filters with a rated pulse frequency of 1.25 or 2.5 kHz should only be operated with a current controller
sampling rate p0115[0] = 400 µs, sine-wave filters with a rated pulse frequency of 2 or 4 kHz with p0115[0] = 250 µs.
The sine-wave filter cannot be selected if the current controller sampling rate has not been appropriately set.
Chassis power units with sine-wave filter are limited to output frequencies of 115 Hz or 150 Hz.
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note:
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
p0233
Power unit motor reactor / PU mot reactor
VECTOR_G
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [mH]
1000.000 [mH]
0.000 [mH]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......