2 Parameters
2.2 List of parameters
SINAMICS G130/G150
246
List Manual (LH2), 07/2016, A5E03263479A
The maximum speed without protection is calculated as follows:
p1082 [rpm] <= 11.695 * r0297 / p0316 (or r0334) [Nm/A]
- use a Voltage Protection Module (VPM) in conjunction with the function "Safe Torque Off" (p9601, p9801).
When a fault condition exists, the VPM short-circuits the motors. During the short-circuit, the pulses must be
suppressed - this means that the terminals for the function "Safe Torque Off" must be connected to the VPM.
- activating the internal voltage protection (IVP) with p1231 = 3.
Description:
Maximum excitation current of the induction motor referred to the permissible rated current of the power unit
(r0207[0]).
Dependency:
Only effective for vector control.
Refer to: p1401, p1573
Note:
The parameter is pre-assigned in the automatic calculation for chassis power units.
Description:
Displays the operating hours for the corresponding motor.
The motor operating time counter continues to run when the pulses are enabled. When the pulse enable is
withdrawn, the counter is held and the value saved.
Dependency:
The following prerequisites must be fulfilled in order to be able to save the operating hours counter in a non-volatile
fashion:
- firmware with V2.2 or higher.
- Control Unit 320 (CU320) with hardware version C or higher (module with NVRAM).
Refer to: p0651
Refer to: A01590
Note:
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter in p0650 can only be reset to 0.
The operating hours counter only runs with motor data set 0 and 1 (MDS).
Description:
Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate message is output when the operating hours set here are reached.
Dependency:
Refer to: p0650
Refer to: A01590
Note:
For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with motor data set 0 and 1 (MDS).
p0644[0...n]
Current limit excitation induction motor / Imax excitat ASM
VECTOR_G (n/M)
Can be changed:
C2, U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
50.0 [%]
300.0 [%]
300.0 [%]
p0650[0...n]
Actual motor operating hours / Mot t_oper act
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [h]
4294967295 [h]
0 [h]
p0651[0...n]
Motor operating hours maintenance interval / Mot t_op maint
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [h]
150000 [h]
0 [h]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......