SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
949
2 Parameters
2.2 List of parameters
Description:
Sets the tolerance for checking the actual values.
For an incremental encoder, the actual values are checked after referencing; for an absolute encoder, when
switching on.
Dependency:
Refer to: C01711
Note:
A change only becomes effective after a POWER ON.
For linear axes, the maximum value is limited to 1 mm.
Description:
Sets the filter time for the SSM feedback signal to detect standstill (n < nx).
Note:
The filter time is effective only if the function is enabled (p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description:
Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" (SGA n < n_x) is set.
For p9568 = 0, the value in p9546 is also applicable for SAM/SBR.
Caution:
The following applies for p9506 = 3:
The "SAM/SBR" function is deactivated if the selected threshold value is undershot.
Note:
F-DO: Failsafe Digital Output / SGA: Safety-related output
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
SSM: Safe Speed Monitor (safety-related feedback signal from the velocity monitoring) / SGA n < nx: Safety-related
output n < nx
p9544
SI Motion actual value comparison tolerance (referencing) (CU) / SI Mtn ref tol
VECTOR_G (Safety
rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0000 [°]
36.0000 [°]
0.0100 [°]
p9545
SI Motion SSM (SGA n < nx) filter time (Control Unit) / SI Mtn SSM filt CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2823
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
500.00 [ms]
0.00 [ms]
p9546
SI Motion SSM (SGA n < nx) velocity limit (CU) / SI Mtn SSM v_limCU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2823
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [mm/min]
1000000.00 [mm/min]
20.00 [mm/min]
Summary of Contents for SINAMICS G130
Page 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Page 2: ......
Page 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Page 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Page 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Page 1975: ......